SUNX Limited MJE-SF4B01 No.0005-03V
-
23
-
2-4
Mounting
2-4-1 Mounting of the Mounting Bracket
<Reference>
Mount the emitter and the receiver at the same level and parallel to each other. The effective aperture angle of
this device is ±2.5° or less for a sensing distance exceeding 3m.
Unless otherwise specified, the following mounting procedure is common for both emitter and receiver. For the
preparation of the mounting, prepare the mounting holes on the mounting surface by referring to ‘
6-3
Dimensions
’.
<In case of using standard mounting bracket (MS-SFB-1) (optional)>
1. Loosen the hexagon-socket head bolt for alignment [M4 (length: 6mm)] of the standard
mounting bracket.
2. As shown in the figure below, adjust the direction of this device and that of installation
surface by declining the bracket, and tighten and fix the hexagon-socket head bolt for
alignment. The tightening torque should be 2N
㨯
m or less.
For selecting the appropriate mounting bracket matched to the installation environment,
the mounting bracket is not incorporated in this device. Please purchase the optional
mounting bracket to fit on the mounting environment.
Do not apply the load such as forced bending to the cable of this device. Applying improper
load could cause the wire breakage.
The minimum bending radius of the cable
SFB
- is R6mm. Mount the sensor considering
the cable bending radius.
When this device is used as safety equipment for press machines in Japan, be sure to
use the cable with protective tube (
SFPB
- ) (optional). The minimum bending radius of
the
SFPB
- is R55mm (When the cable protective tube is fitted). Mount the sensor
considering the cable bending radius.