7.10 Clean
Enter setup of “Clean” function. Select the icon to turn on or turn off the clean function. Select
“Auto” to turn on the function as automatic. Set the timer for the clean function to
automatically turn cleaning on or off, and then set the Hysteresis value (Hys.).
Note: When the clean function is turned on, if any value is set to 0, the instrument will automatically
turn off this function. When the clean function is activated under measurement mode, a “Clean
Running” message will show on the top of the display. The measurement value will remain at the last
measured value before cleaning. When entering settings menu or calibration menu while the clean
function is activated, the instrument will automatically stop the cleaning action.
Press
or to select
to activate cleaning test. If
turn ON, the Clean function
will begin and the “WASH”
indicator will light up.
Press to confirm it.
Press to confirm it.
Press to confirm it.
Press
or
to select to activate
cleaning. If turned
off, the menu will
proceed to setup of
Analog.
on
off
on
off
on
off
off
on
on
off
T
on
T
hys
T
off
T
on
T
hys
T
off
T
off
Clean Timer Control
Relay
Contact
Timer
Settings
Measure-
ment
Press or
to adjust Clean Hysteresis
(Hys.) time.
Enter “Analog” Setup
Press to confirm it.
Press to confirm it.
Press to confirm it.
Press
or
to adjust the
cleaning ON
duration.
Press to
confirm minutes
and proceed to
seconds.
Press
or
to adjust the
cleaning OFF
duration.
Press to
confirm minutes
and proceed to
seconds.
30