【M Series】Multi-turn Electric Valve Actuator
57
2021.06
Push Button
Function
Back to previous level to quit.
Switch menu item (up).
Switch menu item (down).
Save the change.
Symbol “
” in front of the item represents current setting.
Only “Digital Permanet”, “Digital Plus” and “Analog Input” Channels need to set
channel 1 or 2. Modbus and Profibus do not need to set.
After setting the channel of “Analog Input”, “Analog Channel” (refer to section 8.8.2)
need to be set as well.
Two signal types for Digital Control: "Digital Permanent" and “Digital Pulse”.
Function
Digital Control
Digital Permanent
Digital Pulse
Run Close
V
V
Stop
V
V
Run Open
V
V
ESD
V
∆
Disable Close
V
∆
Disable Open
V
∆
∆ : It is needed to have a continuous signal to activate. When "Digital Pulse" is se-
lected, it only works in the pulse rise time.
"Digital Permanent" is a continuous signal mode, which means that actuator will oper-
ate when a continuous signal is present.
It is needs to set “NO” (Normal Open) or “NC”(Normal Close) (refer to section
8.8.3) as well.
"Digital Pulse" is the trigger mode, which means that actuator will operate when a
pulse signal is present.
A signal will be trigged when the pulse rise edge is received.
Once any stop signals are received such as manual override enable, torque over-
load and so on, a pulse signal needs to be present again to continue the opera-
tion.
While the “ESD”, “Disable Close” or “Disable Open” is actived, the “Run
Close”, “Stop” and “Run Open” functions will be invalid.
Summary of Contents for M Series
Page 1: ...SY04 C001A EN APP iOS Android ...
Page 7: ... M Series Multi turn Electric Valve Actuator 4 2021 06 3 2 Nameplate Instruction Caution ...
Page 24: ... M Series Multi turn Electric Valve Actuator 21 2021 06 Settings Menu 8 1 2 ...
Page 25: ... M Series Multi turn Electric Valve Actuator 22 2021 06 ...
Page 26: ... M Series Multi turn Electric Valve Actuator 23 2021 06 ...
Page 75: ......