【M Series】Multi-turn Electric Valve Actuator
47
2021.06
Push Button
Function
Back to previous level to quit.
Switch menu item (up).
Switch menu item (down).
Save the change.
While the input signal is failed and the "Signal Fault Mode" is set in "Emergency Po-
sition". The actuator will run to the position set in "Signal Fault Position".
Setting range is from 0 to 100% and default setting is 0%.
Torque Setting
8.7.3
Push Button
Function
Back to previous level to quit.
Adjust tripping torque in end position.
One push corresponds to 10% reduction.
Adjust tripping torque in end position
One push corresponds to 10% increase.
Save the change.
The tripping torque in end position CLOSE and OPEN could be set from
30 % to 100 % and default settings are 100% for Close and 50% for Open.
The function must be applied with “Close / Open End Stop Mode” and “Close / Open
Position Range”. And, the End Stop Mode is set in “Torque” priority.
No.
Menu
Lowest User
Level
6.3.1
End Torque (Close)
User
6.3.2
End Torque (Open)
User
6.3.3
Over Torque (Close)
User
6.3.4
Over Torque (Open)
User
[Signal Fault Position]
[End Torque (Close)/(Open)]