【M Series】Multi-turn Electric Valve Actuator
31
2021.06
The actuator is not operated in the following condition and warning message will be
shown on the display.
Warning Message
Description
a
Main Power Fault
Main power failure (AC power failure).
b
Please Set Limit Range
Abnormal Open / Close Limit setting or Open /
Close limits are not set.
c
Handwheel Fault
Handwheel sensor signal failure.
d
Handwheel Open
Handwheel lever open.
(At Manal Operation status)
e
Encoder Fault
Encoder sensor signal failure.
f
Driver Comm. Error
Abnormal motor driver module.
g
Motor Drive Fault
Abnormal motor running.
h
Motor Temp. Fault
Motor temperature sensing signal failure.
i
MotorOverheat(Stop)
Motor temperature higher than 135
℃
(275
℉
).
j
Driver Overheat
Motor power module (IGBT) temperature higher
than 125
℃
(257
℉
).
k
EEPROM Fault
The PCBA module failure to save the data.
The following warning messages will be shown on the display but the motor still can be
operated.
Warning Message
Operating Condition
a
Over Limit Range
When actuator exceeds the limit value set in the
running direction, it needs to be operated in the
opposite direction.
b
Motor OH
(Speed Limit)
Motor temperature is higher than the setting
value thus the actuator is running at the lowest
speed.
c
Close Overload
Open Overload
When the torque switch is activated, the motor
will be stopped. The actuator could be operated
“Only” in the opposite direction.
When Encoder failure, the backup Encoder will start running to keep saving the travel
position during manual operation.
[
Local Operation - Stop
]
Summary of Contents for M Series
Page 1: ...SY04 C001A EN APP iOS Android ...
Page 7: ... M Series Multi turn Electric Valve Actuator 4 2021 06 3 2 Nameplate Instruction Caution ...
Page 24: ... M Series Multi turn Electric Valve Actuator 21 2021 06 Settings Menu 8 1 2 ...
Page 25: ... M Series Multi turn Electric Valve Actuator 22 2021 06 ...
Page 26: ... M Series Multi turn Electric Valve Actuator 23 2021 06 ...
Page 75: ......