![Sumitomo HC-4A Technical Manual Download Page 56](http://html1.mh-extra.com/html/sumitomo/hc-4a/hc-4a_technical-manual_1390617056.webp)
Troubleshooting
50
5.
With an ohmmeter, check the resistance across compressor terminals C and S. Resistance
should be 1.8 to 2.2 ohms. If the resistance is outside this range, consult a SCAI Service
Center. If there is no continuity, the winding is open. Consult a SCAI Service Center.
6.
With an ohmmeter, check for continuity between compressor terminal C and one of the
copper tubes entering the compressor housing. If there is continuity, the motor is grounded.
Consult a SCAI Service Center.
7.
If the motor passes these electrical checks, reconnect wires 7, 8, and 9 to compressor
terminals C, M, and S respectively.
8.
Replace the terminal box cover and the cover of the compressor module, unless current
measurement is to be performed.
Figure 7 Compressor Terminals
Current Measurement
Tools required: #2 Phillips screwdriver
Clamp-on ammeter
1.
Disconnect the power to the compressor
2.
Remove the wiring terminal block access cover from the front panel.
3.
Locate the incoming power leads at the terminal block.
4.
Expose the power leads enough to use a clamp-on ammeter.
5.
Clamp the ammeter on one of the power leads.
6.
Reconnect the power to the compressor.
7.
Start the compressor.
S
C
M
Temperature
Overload Switch
Compressor Motor
Terminals
Summary of Contents for HC-4A
Page 2: ......
Page 6: ...iv This page is intentionally blank ...
Page 10: ...4 This page is intentionally blank ...
Page 12: ...6 This page is intentionally blank ...
Page 14: ...8 This page is intentionally blank ...
Page 36: ...30 This page is intentionally blank ...
Page 38: ...32 This page is intentionally blank ...
Page 59: ...Troubleshooting 53 Figure 8 HC 4A Wiring Diagram Main Electrical Chassis and Components ...
Page 60: ...Troubleshooting 54 Figure 9 HC 4A2 Wiring Diagram Main Electrical Chassis and Components ...
Page 61: ...Troubleshooting 55 Figure 10 HC 4A and HC 4A2 Wiring Diagram Air Cooled Unit ...
Page 62: ...Troubleshooting 56 Figure 11 HC 4A Electrical Schematic ...
Page 64: ...Troubleshooting 58 Figure 13 HC 4A2 Electrical Schematic Air Cooled Unit ...
Page 68: ...Parts 62 Figure 15 Parts Identification for HC 4A 12 14 19 23 ...
Page 69: ...Parts 63 Figure 16 Parts Identification for HC 4A2 12 14 19 23 ...
Page 70: ...Parts 64 Figure 17 Parts Identification 29 28 30 31 ...