OPERATING MANUAL FOR SELECT EDI 60
L300180 Iss:A
23
Data is stored to the data stick as a .CSV file which may be viewed
using Microsoft Excel.
“Clear data logger”
After downloading data it is recommended to clear the data logger
memory as it has a limited capacity which when exceeded
historical data will be over written
Selecting and accepting clear data logger clears the data file log.
6.5
Factory Default settings
6.5.1
Setting menu defaults
SETTINGS MENU
Default settings
Date and Time
Set Time
-
Set Date
-
Set Format
DD/MM/YY
Alarms
Audio Alarm Enable
Enable
Permeate Quality Alarm
15 uS
Permeate Temperature Alarm
35
o
C
Rinse Temperature
30°C
Maintenance
Pre-treat (PT) Pack date
-
6.5.2
System menu defaults
SYSTEM MENU
Default settings
Product Information
-
Engineer menu
-
Set Unit ID
00
Auto Restart
Disabled
Log Frequency
30 Minutes
Data Transfer
-
Upload Files
-
Clear Logger
-