background image

REQUIREMENTS FOR INSTALLATION

Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part for 

residential purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent termination 

is less than seven (7) feet above finished grade in the area of the 

venting, including but not limited to decks and porches, the following 

requirements shall be satisfied:

1.

  INSTALLATION OF CARBON MONOXIDE DETECTORS.  

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter shall 

observe that a hard wired carbon monoxide detector with an 

alarm and battery back-up is installed on the floor level where 

the gas equipment is to be installed.  In addition, the installing 

plumber  or gas  fitter shall  observe  that a battery operated  or 

hard wired carbon monoxide detector with an alarm is installed 

on each additional level of the dwelling , building or structure 

served by the side wall horizontal vented gas fueled equipment.  

It shall be the responsibility of the property owner to secure the 

services of qualified licensed professionals for the installation of 

hard wired carbon monoxide detectors.

a.

  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard wired carbon monoxide detector with alarm and battery 

back-up may be installed on the next adjacent floor level.

b.

  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply with 

the above requirements; provided, however, that during said 

thirty (30) day period, a battery operated carbon monoxide 

detector with an alarm shall be installed.

2.

  APPROVED CARBON MONOXIDE DETECTORS.  Each 

carbon monoxide detector as required in accordance with the 

above provisions shall comply with NFPA 720 and be ANSI/UL 

2034 listed and IAS certified.

3.

    SIGNAGE.   A  metal  or  plastic  identification  plate  shall  be 

permanently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment.  The sign shall read, in print size 

no less than one half (½) inch in size, 

“GAS VENT DIRECTLY 

BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”

.

4.

  INSPECTION.  The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment shall not approve 

the installation unless, upon inspection, the inspector observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:

1. 

 The equipment listed in Chapter 10 entitled “Equipment Not 

Required To Be Vented” in the most current edition of NFPA 54 

as adopted by the Board; and 

2.

  Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 

dwelling, building or structure used in whole or in part for 

residential purposes. 

UNIT START - UP

WARNING!  

Failure to follow these instructions may lead to a fire, explosion, property 

damage, personal injury, or loss of life.

 

CAUTION:

 This furnace is equipped with a direct ignition control  Do not 

attempt to manually light the burners.

BEFORE OPERATING, 

smell all around the appliance area for gas.  Be 

sure to smell next to the floor because gas is heavier than air and will 

settle on the floor.  If you smell gas STOP.  Open the windows and doors 

to clear out any gas.  Recheck all gas piping and connections for leaks.

TO CHECK THE UNIT OPERATION:
1.

  Make sure the gas valve is switched ON.  Remove the gas 

compartment door.  Turn the gas valve knob or move the switch 

to the ON position.  See figure 5.  Do not use any tools to turn the 

knob.  If you are unable to push in and turn the knob by hand then 

call a qualified service technician for assistance.  Replace the gas 

compartment door.

2.

  Turn on electrical power to the unit.

3.

  Switch the room thermostat to heat.

4.

  Raise the set point to above the room temperature.

5.

  The thermostat will call for heat and the combustion blower will 

begin to operate.

6.

  The combustion blower will operate for 15 to 20 seconds before 

the ignition controls begins sparking, then the gas valve will open 

and the burners will light.  The burners can be viewed through the 

sight glass in the door panel.

7. 

The room air blower starts 30 seconds after the burners light.

8.

  Once the room reaches the set temperature, the burners turn off 

and the room air blower turns off 90 seconds later.

9.

  Switch the room thermostat over to cooling.

10.

  Lower the set point to below the room temperature.

11.

  After a slight delay the room air blower will begin to run and the 

compressor will start.  Note:  There will be a 5 minute delay in the 

compressor starting if the thermostat set point was raised and then 

lowered again.

12.

  Once the room reaches the set temperature, the compressor will 

turn off and the room air blower will turn off 30 seconds later.

TO SHUT DOWN UNIT

To turn off the unit switch the room thermostat to OFF.  Turn the electrical 

power off and close the manual gas supply valve before performing any 

service to the unit.

HEATING ADJUSTMENTS

1.

 

Turn off the unit at the room thermostat and shut off the manual gas valve.  

2.

 

Connect a pressure gauge with suitable range (0 to 10” for natural and 0 to 

15” for LP) to the inlet pressure port on the gas valve.  See figure 5.

3.

 

Open the manual gas valve and turn the unit on.

4.

  Once the furnace is operating, check the inlet gas pressure.  Adjust the 

pressure regulator to obtain an inlet pressure of  5” to 10” water column for 

natural gas and 11” to 13” for LP gas.

5.

 

Turn off the unit and shut off the manual gas valve.

6.

 

Move the pressure gauge to the manifold pressure port on the gas valve.  

See figure 5.

7.

 

Once the furnace is operating, check the manifold pressure.  Adjust the gas 

valve pressure regulator to obtain a manifold pressure of 3.5” water column 

for natural gas and 10.0” water column for LP gas. 

8.

  On natural gas installations the input to the furnace must be checked to 

insure safe operation.  Any other gas appliances that use the gas meter 

must be turned off including the pilot lights.  

9.

 

With the Dynapack furnace running, count the time it takes for the gas meter 

to make one revolution.  Also record the gas meter rate of cubic feet per 

revolution.  You will also need the average heating value of the natural gas 

for your location.  Plug these factors into the equation below to calculate the 

gas input rate to the furnace in BTU per hour.

BTU/HR Input =

Cubic Feet Per 

Revolution

X 3600 X Heating 

Valve

Number of Seconds Per 

Revolution

10.

  Your recorded value on input must be or- 2% of the rated input.  If it 

is not then adjust the manifold pressure lower to reduce the input or higher 

to increase the input.  Do not go outside of 3.2” to 3.8” water column.

11.

  The only adjustment for LP gas is to maintain the 10” water column manifold 

pressure.

12.

  Turn off the unit, close the manual gas valve, and remove the pressure 

gauge.  Make sure the gas valve pressure port plug screws are tightened 

along with the gas valve regulator cap.  Replace the burner compartment 

door.

13. 

Open the manual gas valve and turn on the furnace.

14. 

Place a thermometer in the return air along with one in the supply air 

as close to the furnace as possible.  Once the supply air temperature is 

constant, record both temperatures.  Subtract the return air temperature 

from the supply air temperature.  This difference is the temperature rise of 

the furnace.  

15.

  Compare the measured temperature rise to the nameplate range.  If the 

measured rise is lower than the nameplate minimum, then select the next 

lower blower speed for the heating speed.  If the measured temperature rise 

is above the nameplate maximum, then select the next higher blower speed 

for the heating speed.

16.

  If a new blower speed was selected then re-measure the temperature rise 

and repeat the adjustment if needed.

COOLING ADJUSTMENTS

The only cooling adjustment that can be made is in the blower speed.   

1.

 

Turn the unit on in the cooling mode and allow to operate until stable.

2.

 

Place a thermometer in the return air opening and another in the supply air 

opening as close to the unit as possible.  

3. 

The a/c unit must operate until condensate water is coming off of the 

evaporator coil.  Measure the return and supply air temperatures.

4.

 

Proper cooling operation is obtained if there is a 20 degree Fahrenheit drop 

in air temperature through the a/c unit.

5

Summary of Contents for DYNAPACK S Series

Page 1: ...the National Safe Transit Test This means that the packaged product with normal handling will withstand the load conditions encountered in normal transit and in handling Your unit should be inspected...

Page 2: ...ack unit has been safety certified by Intertek Testing Services to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural or LP gas The Dynapa...

Page 3: ...y out side or turned inside and routed to the building drain system If the wall sleeve drain is routed to the building sewer system then it must be trapped to prevent sewer gasses from escaping ELECTR...

Page 4: ...is recommended that a 5 conductor thermostat wire be used in case the room thermostat needs power from the unit transformer The low voltage pigtails for the thermostat wiring must be routed to the ou...

Page 5: ...at will call for heat and the combustion blower will begin to operate 6 The combustion blower will operate for 15 to 20 seconds before the ignition controls begins sparking then the gas valve will ope...

Page 6: ...tion for both the USA and Canada Call Technical Service at 423 775 2131 for installations above 4500 feet OPERATION IN EXTREME COLD OR SNOWY AREAS In those areas where the ambient temperature is consi...

Page 7: ...le Bronze Finish DYPA30AC1A and DYPA36AC1A 521051 LP Conversion Kit All Models 36 000 BTU input 48 000 BTU input 60 000 BTU input 1741 5 7 8 Wall Sleeve Kit DYPA12 DYPA18 and DYPA24 1736 5 7 8 Wall Sl...

Page 8: ...G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O NOTE 1 Y BK PK BL BL LIMIT BLOWER R O...

Page 9: ...3m a D VERTICAL CLEARANCE TO VENTILATED SOFFIT LOCATED ABOVE THE TERMINAL WITHIN A HORIZONTAL DISTANCE OF 2 FEET 61cm FROM THE CENTER LINE OF THE TERMINAL a a M CLEARANCE UNDER VERANDA PORCH DECK OR B...

Page 10: ...sponsibility and liability of the owner An owner requesting performance under this Warranty shall provide reasonable access to the allegedly defective or malfunctioning product or part to Airxcel Comm...

Page 11: ...ng wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 Insert...

Page 12: ...iphon en T dans le tuyau de drainage en caoutchouc L utilisation d eau savonneuse peut faciliter l insertion 10 Alignez le siphon en P selon le besoin par rapport la plomberie de drainage existante 11...

Page 13: ...n tel service seront assum s par le demandeur Un propri taire requ rant une intervention ce titre dans le cadre de la garantie devra permettre un acc s raisonnable au produit ou la pi ce incrimin e po...

Page 14: ...ITU ES SUR DES PROPRI T S PUBLIQUES 7 PIEDS 2 13 cm a D ESPACE LIBRE LA VERTICALE PAR RAPPORT AU PAREMENT VENTIL SITU AU DESSUS DE LA SORTIE a a M ESPACE LIBRE SOUS LES V RANDAS LES PROCHES LES PATIOS...

Page 15: ...L ALLUMEUR CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAMME 24V FLAMME INTERRUPTEUR BL O 230V INDUCER BK R OFM C BK BR WHT VANNE GAZ FIN DE COURSE HAUTE PRESSOSTAT INTERRUPTEUR MISE EN APPLICATION O...

Page 16: ...DYPA36AC1A 521051 Trousse de conversion au GPL tous les mod les Entr e de 36 000 BTU entr e de 48 000 BTU et entr e de 60 000 BTU 1741 Support mural de 5 7 8 po DYPA12 DYPA18 and DYPA24 1736 Support...

Page 17: ...nt un but particulier et il ne faut pas les trafiquer en changeant leur emplacement ou par un c blage sp cial Si la fournaise ne fonctionne pas si le ventilateur de l air ambiant ne se met pas en marc...

Page 18: ...z l appareil sous tension 3 Placez le thermostat de la pi ce en position de chauffage 4 Augmentez le r glage au dessus de la temp rature ambiante 5 Le thermostat demandera du chauffage et le ventilate...

Page 19: ...de l appareil doit tre v rifi Ne d passez pas lb po ca de pression manom trique ou 14 po CE pour ce test autrement la vanne gaz pourrait tre endommag e MISE EN GARDE Suburban ne recommande pas d utili...

Page 20: ...ou d entretien ALIMENTATION EN GAZ Tous les appareils Dynapack sont con us pour utiliser du gaz naturel L appareil doit tre converti au GPL l aide la trousse de conversion du fabricant si l appareil d...

Page 21: ...ons pr sent es dans ce manuel Les appareils Dynapack sont des ensembles verticaux contenant un chauffage au gaz et une climatisation l lectricit Les appareils Dynapack sont certifi s au plan de la s c...

Page 22: ...stall uniquement l aide des accessoires approuv s grille d ext rieur et manchons muraux Le non respect de ces instructions peut entra ner des dommages mat riels des blessures et m me la mort MISE EN G...

Reviews: