GAS PIPING
The Dynapack unit has a ½” pipe connection for the gas line. The size
of the gas piping must be based on the length of the run and not the
connection size. See table 5 for reference pipe sizing.
Consult with the local gas utility or code authority for gas piping instal-
lation.
If local codes allow the use of a flexible gas appliance connector,
always use a new listed connector. Do not use a connector which has
previously serviced another gas appliance.
The gas piping should contain a manual shut off valve with test port
near the furnace in addition to a drip leg and a ground joint union for
servicing. The test port needs to be upstream of the manual shut off
valve for leak testing and adjusting the supply pressure regulator.
The manual shut off valve must be rated for the gas piping test pressure.
If not, then the shut off valve must be removed from the piping system
during testing. Once the gas piping up to the shut off valve has been
tested, the remaining piping to the unit gas valve must be tested. Do
not exceed ½ psig or 14” water column for this test or the gas valve may
be damaged.
CAUTION:
Suburban does not recommend the use of flex tubing to
make the gas connections to the unit unless the flex tubing is a high
quality stainless certified by CSA and approved for use by local code.
WARNING!
A pipe thread compound resistant to the action of liquefied petroleum (LP)
and natural gas must be used on all pipe joints.
WARNING!
The gas valve supplied with this furnace is rated at 1/2 psig maximum. Any
higher pressure may rupture the pressure regulator diaphragm and may cause over firing
of the burners and improper burner operation. The over firing may result in the creation of
carbon monoxide which could cause asphyxiation.
WARNING! FIRE OR EXPLOSION HAZARD!
Failure to follow the safety warning
exactly could result in serious injury, death, or property damage.
WARNING!
Never test for gas leaks with an open flame. Use a commercially available
soap solution made specifically for the detection of leaks to check all connections. A fire or
explosion may result causing property damage, personal injury, or loss of life.
CONTROL WIRING
The room thermostat should be installed on an interior wall and near the
return air for the unit. It is recommended that a 5 conductor thermostat
wire be used in case the room thermostat needs power from the unit
transformer.
The low voltage pigtails for the thermostat wiring must be routed to
the outside of the Dynapack unit for connection. The Dynapack unit
contains a second knockout above the control box for this purpose.
The National Electrical Code requires that low voltage wiring be kept
separate from high voltage wiring and cannot be routed through the
same knockout or conduit. Local codes may also require that an
electrical box be installed on the low voltage knockout to contain the
electrical connections.
Follow the thermostat manufacturers instructions for mounting and
wiring. The low voltage is grounded inside the unit control box. See the
attached wiring diagram on page 8.
VALVE ON/OFF SWITCH
INLET PRESSURE POST.
TEST HOSE GOES OVER
OUTSIDE OF POST.
USE
3
32
" HEX WRENCH
TO OPEN ONE TURN.
OUTLET PRESSURE POST.
TEST HOSE GOES OVER
OUTSIDE OF POST. USE
3
32
" HEX WRENCH TO OPEN
ONE TURN.
INLET
1
2
" NPT
REGULATOR ADJUSTMENT
BENEATH THIS SCREW COVER
Figure 5
4
INDOOR CFM vs STATIC PRESSURE (Dry coil + no air filter)
Model Number
Blower
Speed
0.10" wc
0.15" wc
0.20" wc
0.25" wc
0.30" wc
0.40" wc
0.50" wc
0.60" wc
0.70" wc
0.80" wc
DYPA12AC1A***
LO
497
473
448
424
400
348
296
247
212
160
MED LO
577
562
547
522
497
458
415
357
317
281
MED
757
748
739
716
692
670
635
586
558
521
MED HI
937
920
905
888
872
852
827
790
728
677
HI
1060
1050
1042
1015
977
927
876
824
758
700
DYPA18AC1A***
LO
512
491
469
428
387
320
285
250
213
179
MED LO
596
568
540
522
504
447
415
381
324
291
MED
773
761
748
730
711
675
640
622
586
550
MED HI
972
955
938
927
915
874
850
825
796
766
HI
1108
1091
1074
1057
1039
1002
970
917
868
796
DYPA24AC1A***
LO
504
483
461
420
379
312
252
207
N/R
N/R
MED LO
588
560
532
514
496
439
377
320
262
202
MED
765
753
740
722
703
667
622
572
532
482
MED HI
964
947
930
919
907
866
828
782
757
702
HI
1100
1083
1066
1049
1031
994
962
922
882
827
DYPA30AC1A***
LO
490
465
440
415
385
310
225
170
N/R
N/R
MED LO
570
540
520
500
476
415
365
310
250
205
MED
768
755
741
732
704
666
621
580
535
500
MED HI
934
922
913
895
873
835
800
760
730
690
HI
1064
1046
1017
1009
995
965
935
900
875
828
DYPA36AC1A***
LO
490
465
440
415
385
310
225
170
N/R
N/R
MED LO
570
540
520
500
476
415
365
310
250
205
MED
768
755
741
732
704
666
621
580
535
500
MED HI
934
922
913
895
873
835
800
760
730
690
HI
1064
1046
1017
1009
995
965
935
900
875
828
TABLE 2