background image

INSTALLING AND SECURING UNIT

TO WALL SLEEVE

Before installing and securing the unit to the wall sleeve, make sure 

that the proper grille kit is installed.  Due to the temperatures of the 

combustion products released from the gas vent, DynaPack gas package 

units require the use of an aluminum grille kit (see ACCESSORIES on 

page 7).

1.

 

Double check the installation of the wall sleeve to make sure it is securely 

attached to the wall opening.  Inspect the wall sleeve drain for proper 

installation if an inside drain is being used.  

2. 

Examine the gaskets on the wall sleeve to make sure there is a continuous 

seal between the wall sleeve and the unit.

3.

 

Place DynaPack unit onto the wall sleeve.  Lift the unit 3/4" and place over 

the wall sleeve base (see Figure 3).  A PALLET JACK works well for this.  

Temporarily block the unit up and install front leveling bracket (see Figure 

3).  Adjust leveling legs to level.

4. 

Use the two retaining straps to secure the unit to the wall sleeve (see Figure 

3).  Verify that the gaskets of the wall sleeve make a complete seal to the 

unit paying particular attention to top and bottom corners of the unit to 

sleeve seal.  Caulk if needed.

DUCT WORK 

The duct work for the dwelling should be designed for the lowest 

possible static pressure to reduce energy usage and noise.  Table 2 lists 

the approximate cfm delivery of the units on each of the indoor blower 

speeds.  Table 4 lists the recommended heating and cooling speeds 

with its approximate cfm delivery.  Use both tables to properly design 

the duct system for both heating and cooling cfm.

AIR FILTER

The Dynapack unit is equipped with a permanent, cleanable air filter.  

This filter can be used if the unit is installed so that the filter is accessible 

to the homeowner.  The permanent filter installed inside the unit must 

be removed and discarded if a disposable filter is installed in the return 

air  duct.    See  Table  3  for  the  minimum  filter  area  required  for  the 

Dynapack unit based on unit capacity.  It is recommended that air filters 

be cleaned or replaced monthly to keep the cooling coil and interior duct 

surfaces clean and able to operate most efficiently.  Optional MERV 13 

filters are available.

MINIMUM REQUIRED SURFACE AREA FOR 

DISPOSABLE FILTERS

MODEL NUMBER

FILTER AREA

DYPA12

288 square inches

DYPA18

288 square inches

DYPA24

480 square inches

DYPA30 & DYPA36

480 square inches

TABLE 3

CONDENSATE DRAIN

The Dynapack unit and wall sleeve each have there own drain.  The unit 

drain is for the condensate developed by the evaporator coil.  It needs 

to be trapped and routed to the building drain system.  Use ¾” pvc pipe 

and fittings (field supplied).  

The wall sleeve is equipped with a drain pan that collects rain water 

entering the wall sleeve and the unit condenser coil area.  At the time 

of installation of the wall sleeve, this drain can be directed directly out-

side or turned inside and routed to the building drain system.  If the 

wall sleeve drain is routed to the building sewer system then it must be 

trapped to prevent sewer gasses from escaping.

ELECTRICAL CONNECTIONS

The Dynapack unit is approved using copper conductors only.  See the 

unit data plate for unit minimum circuit ampacity.  Size the wire based 

on the unit circuit ampacity, type of wire used, and method of wiring, in 

conduit or open.  If the electrical supply is 208 volt, then do not exceed 

3% voltage drop based on the length of wire run.  See the National 

Electrical Code or the Canadian Electrical Code for more information.

The typical electrical supply is two phase wires where voltage measured 

is 208-230 volts phase to phase.  An additional wire for unit grounding 

is required.  See the unit data plate for the maximum fuse or circuit 

breaker size.  It is recommended that time delay fuses or a two pole 

HACR breaker be used in order to prevent nuisance trips.

Alternately, the Dynapack unit may be wired with one phase wire 

where the voltage measured is 208-230 volts phase to neutral.  In this 

case, the phase wire should be connected to L1 on the contactor.  An 

additional wire for unit grounding is required.

On 208 volt systems the transformer wiring needs to be changed.  Swap 

the red transformer wire for the orange wire for 208 volt operation.

A disconnect should be installed next to the unit so the electrical power 

can be turned off for servicing or maintenance.

GAS SUPPLY

All Dynapack units are built to operate on natural gas.  The unit must 

be converted using the manufacturers conversion kit in order to operate 

on LP gas.

WARNING!  

Any conversion of a natural gas unit to liquefied petroleum (LP) gas must be 

done by qualified personnel using a conversion kit available from the manufacturer, following 

the instructions in the conversion kit,  If done improperly, over firing of the burners and improper 

burner operation can result.  This can create carbon monoxide which could cause asphyxiation.

Minimum gas supply pressure for purposes of input adjustment:

 

 

Minimum 

Maximum

Natural Gas

 

5" W.C. * 

10" W.C.

Liquefied Petroleum (LP) Gas

 

11" W.C. 

13" W.C.

*Water Column

3

#10-24 X 1 

1

2

MACHINE SCREW

LEG LEVELER

38-16 HEX NUT

THE LEVELER BRACKET INSTALLS

INTO UNIT BRACKET AND IS HELD

IN PLACE BY THE UNIT WEIGHT

#12 X .75" DRILL SCREWS

(2 PLACES)

LOCATE BRACKET BY INSTALLING

THE TAB UNDER THE UNIT BASE

AND ABOVE THE BASE RAIL.

TINNERMAN CLIP

ATTACH BRACKET TO UNIT

WITH (2) #10 X 1/2" DRILL SCREWS

(2 ON EACH BRACKET)

ENGAGE FLANGE ON WALL SLEEVE

WITH FLANGE ON STRAP.  TIGHTEN

MACHINE SCREWS UNTIL BRACKET

CAN BE SECURED TO UNIT WITH

DRILL SCREWS.

RETURN

SUPPLY

ACCESS PANEL 

TO 

CONTROLS

ACCESS PANEL 

TO GAS VALVE 

AND BURNERS

ACCESS PANEL 

TO COMPRESSOR 

AND OUTDOOR FAN

DRIP LEG (FIELD SUPPLIED)

MANUAL SHUTOFF VALVE 

WITH 

1

8

"NPT PLUGGED TAPPING,

ACCESSIBLE FOR TEST GAUGE

CONNECTION (FIELD SUPPLIED)

CONDENSATE DRAIN

GROUND JOINT UNION

(FIELD SUPPLIED)

FILTER DOOR

TRAP

ROUTE TO BUILDING DRAIN

ELECTRICAL POWER ENTRANCE

FRONT VIEW

Figure 4

Figure 3

Summary of Contents for DYNAPACK S Series

Page 1: ...the National Safe Transit Test This means that the packaged product with normal handling will withstand the load conditions encountered in normal transit and in handling Your unit should be inspected...

Page 2: ...ack unit has been safety certified by Intertek Testing Services to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural or LP gas The Dynapa...

Page 3: ...y out side or turned inside and routed to the building drain system If the wall sleeve drain is routed to the building sewer system then it must be trapped to prevent sewer gasses from escaping ELECTR...

Page 4: ...is recommended that a 5 conductor thermostat wire be used in case the room thermostat needs power from the unit transformer The low voltage pigtails for the thermostat wiring must be routed to the ou...

Page 5: ...at will call for heat and the combustion blower will begin to operate 6 The combustion blower will operate for 15 to 20 seconds before the ignition controls begins sparking then the gas valve will ope...

Page 6: ...tion for both the USA and Canada Call Technical Service at 423 775 2131 for installations above 4500 feet OPERATION IN EXTREME COLD OR SNOWY AREAS In those areas where the ambient temperature is consi...

Page 7: ...le Bronze Finish DYPA30AC1A and DYPA36AC1A 521051 LP Conversion Kit All Models 36 000 BTU input 48 000 BTU input 60 000 BTU input 1741 5 7 8 Wall Sleeve Kit DYPA12 DYPA18 and DYPA24 1736 5 7 8 Wall Sl...

Page 8: ...G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O NOTE 1 Y BK PK BL BL LIMIT BLOWER R O...

Page 9: ...3m a D VERTICAL CLEARANCE TO VENTILATED SOFFIT LOCATED ABOVE THE TERMINAL WITHIN A HORIZONTAL DISTANCE OF 2 FEET 61cm FROM THE CENTER LINE OF THE TERMINAL a a M CLEARANCE UNDER VERANDA PORCH DECK OR B...

Page 10: ...sponsibility and liability of the owner An owner requesting performance under this Warranty shall provide reasonable access to the allegedly defective or malfunctioning product or part to Airxcel Comm...

Page 11: ...ng wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 Insert...

Page 12: ...iphon en T dans le tuyau de drainage en caoutchouc L utilisation d eau savonneuse peut faciliter l insertion 10 Alignez le siphon en P selon le besoin par rapport la plomberie de drainage existante 11...

Page 13: ...n tel service seront assum s par le demandeur Un propri taire requ rant une intervention ce titre dans le cadre de la garantie devra permettre un acc s raisonnable au produit ou la pi ce incrimin e po...

Page 14: ...ITU ES SUR DES PROPRI T S PUBLIQUES 7 PIEDS 2 13 cm a D ESPACE LIBRE LA VERTICALE PAR RAPPORT AU PAREMENT VENTIL SITU AU DESSUS DE LA SORTIE a a M ESPACE LIBRE SOUS LES V RANDAS LES PROCHES LES PATIOS...

Page 15: ...L ALLUMEUR CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAMME 24V FLAMME INTERRUPTEUR BL O 230V INDUCER BK R OFM C BK BR WHT VANNE GAZ FIN DE COURSE HAUTE PRESSOSTAT INTERRUPTEUR MISE EN APPLICATION O...

Page 16: ...DYPA36AC1A 521051 Trousse de conversion au GPL tous les mod les Entr e de 36 000 BTU entr e de 48 000 BTU et entr e de 60 000 BTU 1741 Support mural de 5 7 8 po DYPA12 DYPA18 and DYPA24 1736 Support...

Page 17: ...nt un but particulier et il ne faut pas les trafiquer en changeant leur emplacement ou par un c blage sp cial Si la fournaise ne fonctionne pas si le ventilateur de l air ambiant ne se met pas en marc...

Page 18: ...z l appareil sous tension 3 Placez le thermostat de la pi ce en position de chauffage 4 Augmentez le r glage au dessus de la temp rature ambiante 5 Le thermostat demandera du chauffage et le ventilate...

Page 19: ...de l appareil doit tre v rifi Ne d passez pas lb po ca de pression manom trique ou 14 po CE pour ce test autrement la vanne gaz pourrait tre endommag e MISE EN GARDE Suburban ne recommande pas d utili...

Page 20: ...ou d entretien ALIMENTATION EN GAZ Tous les appareils Dynapack sont con us pour utiliser du gaz naturel L appareil doit tre converti au GPL l aide la trousse de conversion du fabricant si l appareil d...

Page 21: ...ons pr sent es dans ce manuel Les appareils Dynapack sont des ensembles verticaux contenant un chauffage au gaz et une climatisation l lectricit Les appareils Dynapack sont certifi s au plan de la s c...

Page 22: ...stall uniquement l aide des accessoires approuv s grille d ext rieur et manchons muraux Le non respect de ces instructions peut entra ner des dommages mat riels des blessures et m me la mort MISE EN G...

Reviews: