Page 7 of 51
3. TECNICAL DETAILS
General
Product Identification Number
CE 0063 BP3254
Dimensions (h x w x d)
Mm
835 x 458 x 485
890 x 458 x 670
Classification
II2H3P
Gas Appliance Type
B23; C13X,C23X,C33X,C43X, C53X, C63X,C83X
Boiler Type S-CB
60
80
100
120
150
180
Water content etc.
Ltr
3,9
5
6,5
8,3
10,4
12,9
Weight (empty)
Kg
46
73
78
83
92
101
Gas connection
”
R ¾”
R ¾”
R ¾”
R ¾”
R 1”
R 1”
Co-axial flue connections
mm
80/125
80/125
100/150 100/150 100/150 100/150
Separate Flue Exhaust / Air Inlet
80-80
80-80
100-100
100-100 130-130 130-130
Possible with Adaptor (extra cost)
mm
100-100
130-130
Power consumption
W
355
355
355
375
460
460
Protection class
IP40
IP40
IP40
IP40
IP40
IP40
Central heating
Nominal input (Nett) 80/60ºC
kW
14-56
18-74
23-92
27-111
34-138
43-166
Nominal input (Gross) 50/30ºC
kW
15-61
20-82
25-102
30-123
38-154
48-184
Gas flow max. (G20)
m³/hr
5,9
7,9
9,8
11,8
14,7
17,6
Efficiency at 80/60ºC
%
97
98
98
98
98
98
Efficiency 50/30ºC
%
109
109,5
109,5
109,5
109,5
109,5
Efficiency 40/30ºC RAL 61
%
109,5
110
110
110
110
110
Nominal output at 80/60ºC
kW
55
73
90
109
136
163
Nominal output at 50/30ºC
kW
15-60
20-80
25-100
30-120
36-150
45-180
Norm efficiency 75/60ºC RAL-UZ61
107
107
107
107
107
107
NO x emission, RAL 61
mg/kWh
<15
<15
<15
<15
<15
<15
CO emission, RAL 61
mg/kWh
<20
<20
<20
<20
<20
<20
Table 1: Data
Boiler control includes:
Cascade control for up to 8 boilers ( requires flow temperature sensor at extra cost ) see item
G
page 8
Remote run & fault indication
0-10 VDC control connection ( requires flow temperature sensor at extra cost )
Control for external calorifier primary pump ( pump not included ) via relay at extra cost ( see page 22)
Weather compensation control (with outside detector at extra cost)
Control for an external pump via relay at extra cost,( see page 22 )external pump not included.
Electronic Ignition.
Boiler output modulated between 25% and 100%,
Data
CO2- flue gas
%
9
Dew point combustion gas
°C
53
Temp. Flue gas @ ambient temp 20ºC
°C
85
Flue resistance capability*
Pa
250* up to 600*
PH value condensate
4 to 5,5
Available pressure at 25ºC
mwk
2,5
3
1,5
1,5
1,5
1,5
Max. flow temp.
°C
90
Min./Max. Boiler Pressure
bar
0.5 – 6
Sound level at Maximum Output
dBA
46.0
47.0
48.0
49.0
50.0
50.0
Average Sound level
dBA
32.0
33.0
33.0
34.0
35.0
35.0