Page 11 of 51
Boiler Type S-CB 150 and S-CB 180
150kw and 180kw Boilers are supplied with parallel flue connections
an
adaptor is
available for co axial
flue-ing
at extra cost
6.2.1The installation area must have the following provisions:
•
Items listed in
4
page 8 also see drawings 2.1 page 5 and 2.2 page 6.
•
Electrical point with earth connection;
•
Connection to the drains for condensation water or suitable condense removal device
•
A sound wall or suitable mounting. The wall or frame used for mounting the boiler must be able to hold
the weight of the boiler.
•
Both the air supply (if room sealed) and the flues are to be connected to the outside wall and/or the roof.
(see safety guidelines page 4)
•
Install horizontal Flue parts under 1% fall in the direction of the boiler (one centimetre for every
linear metre)
complete with extra drain points with a 60mm water trap.
•
The installation area must be dry and frost-free and conform to relevant regulations.
•
Installers are advised to choose a part of their building where slight noise emission will not cause
disturbance.
•
A minimum of 15 mbar gas pressure (and or current regulations) all plant running.
890
S-CB
Parallel Flue Co- Axial Flue D
S-CB D D1
150 130 130 100 /150
180 130 130 130 /150
Air inlet Flue
D1 D