IF the setting takes more than 30 minutes the Boiler will return to auto mode. If so, press the SERVICE
button again. Also for returning to the normal menu press SERVICE.
Set the Boiler via measuring the CO2 percentage (as shown in the table 4a below), and gas consumption rate.
Comment:
Measurement of the emissions and CO
2
percentage is via the measuring point in the flue gas pipe, (after
unscrewing the plastic cap).
For gas valve adjustments see illustration on Page 29 Fig. 4
5. Gas consumption
.
Boiler
S-CB-60
S-CB-80
S-CB-100
S-CB-120
S-CB-150
S-CB-180
Natural
gas (G20)
0.098 m³
per minute
0.130 m³
per minute
0.164 m³
per
minute
0.196 m³
per minute
0.245 m³
per minute
0.293 m³
per minute
LPG
See 40&41 See 40&41 See40&41 See 40&41
See 40&41 See 40&41
Table 4, Maximum settings
Type of gas
Natural gas G 20
LPG
Injector
none
none
(Gross)(MJ/m3)
50.7
76.64
Cal. value Net
(MJ/m3)
34
88.00
CO
2
max. Output
(%)
8.8(+/-0.3)*
See LPG
CO
2
min. Output
(%)
8.5(+/-0.3)*
See LPG
* measured without casing
Table 4a Co2 settings