66
FP12 Mundo - Installation and Operation Manual
8.9
Installation Instructions for Masonry Application
WARNING:
BEFORE STARTING THE INSTALLATION, THE MASONRY CHIMNEY MUST BE INSPECTED BY A
QUALIFIED SWEEP.
The following requirements must be respected:
1.
The chimney must be absolutely clear of any soot residue or creosote. Check for cracks, loose or missing
bricks that could inhibit correct installation of the liner.
2.
The clearance to combustible must be a minimum of 1" between the outside of the masonry and any
wood framing or loose insulation.
3.
The chimney must be built in accordance with the current building code.
4.
No other appliance can be connected to the same chimney.
Installation:
The chimney must be relined with a stainless steel liner of the same diameter as the outlet of the
fireplace. For connection at 30
°
or 45° angle, a special connector (B) must be used to connect the liner (C)
to the insulated chimney (A). Verify availability and installation instructions for this connector with the
chimney manufacturer.