FP12 Mundo - Installation and Operation Manual
41
6.3.1.2
On the floor or on a raised base of less than 4" installation (R value for the hearth extension
required)
In the case where the fireplace is installed directly on the floor or on a raised base of less than 4", an R
value for the hearth extension is required. In these case also, the joint between the hearth extension and
the fireplace (
E
) must be protected by a non-combustible material. For example, a sheet metal (not
included).
Note that the floor under of the fireplace should match or exceed the height of the floor protection.
MINIMUM MEASUREMENT
E
2" (51 mm)