52
FP12 Mundo - Installation and Operation Manual
6.3.3.3
Compliance of a Combustible Mantel Shelf
The installation of the combustible shelf is permitted. Refer to Figure 15 in order to locate the safe location.
The shelf shall have a depth (C) up to 12 "(305 mm) and shall be installed 48" (1219 mm) from the firebox
base (B).
In the following illustration, no combustible material is allowed in the area in white.
A
B
C
D
E
F
80"
48"
12" MAXIMUM
8"
12"
9"
6.4
Heat Management Systems
The hot air gravity distribution kit
must be installed
on the FP12 MUNDO.
For installation and safety rules,
see
Appendix 1: Heat Management Systems Installation (AC01375, AC01389 OR AC01363)
.