Parameter tables
Parameters
Para-
meter
Functional description
Setting range
J1=0
J1=1
C 2
Heater controller reset time
0 ... 100 sec
5
C 4
Minimum on-time heater controller for Ux = 2, 24 or 25
0 ... 100 sec
6
C 5
Minimum off-time heater controller for Ux = 2, 24 or 25
0 ... 100 sec
4
C 6
Minimum continuous Analog output for burner heat on Ux = 24.
Clocking will begin, once the minimum output is not reached.
0.0 ... 100.0%
99.9
C 8
Analog output with 2-Point condition OFF
0.0 ...
C9
0.0
C 9
Analog output with 2-Point condition ON
C8
... 100.0 %
100.0
C10
Setpoint S1A
C13
... S1A ...
C14
170.0
C11
Setpoint S1B
C13
... S1B ...
C14
180.0
C13
Setpoint limit low
-199.0 °C ...
C14
0.0
C14
Setpoint limit high
C13
... 999.0 °C
190.0
C16
Temperature guard - Oil
0.0 ... 999.0 °C
205.0
C17
Temperature guard - Wall
0.0 ... 999.0 °C
225.0
C18
Hysteresis temperature guard
0.0 ... 999.0 K
5.0
C20
Mode
0: deactivated
1: TP - (Two point, thermostat)
2: PID - (
C23
: Delta)
2
C21
Current value - sensor selection
1: F01
2: F02
3: F03
4: F04
5: F05
6: F06
7: VF1
8: VF2
9: VF3
10: VF4
11: VF5
12: S1A/B/C (C-level)
1
C22
Setpoint - Target value
0: absolute = 0
(
C23
Absolute value)
1: S1A/B/C (C-Level)
2: S2A/B (E-Level)
1
C23
Setpoint offset
-199.0 ... 999.0 °C [Unit
C21
]
0.0
C24
Hysteresis
0.1 ... 100.0 °C [Unit
C21
]
2.0
C25
Offset; 0%: single-sided (towards off); 50%: Symmetrical
0.0 ... 100.0 %
0.0
C30
PID Function mode
0: Deactivated
+1: P
+2: I
+4: D
+8: Averaged over Period
7
C34
Proportional band (P-band)
0.1 ... 999.0 K [Unit
C21
]
15
C35
Reset time Tn (I-time)
0 ... 999 s
500
C36
Lead time Tv (D-time)
0 ... 999 s
50
C37
PID Backtracking
0.00 ... 2.00
0.00
C38
PID cycle time
This time is also used for the slow PWM available on Ux = 23, 24
1 ... 900 sec
10
C39
PID_OUT MAX (
C20
= 2)
0.0 ... 100.0 %
100.0
C53
Buzzer time at end of special process
0 ... 999 sec
10