Parameter tables
b--
Buttons / Digital Inputs:
T1
1
2
3
4
5
6
7 8 9 10 11 12 13
T2
T3
T4
T5
T6
T7
The controller can optionally be equipped with buttons and a display. The parameters
b1
...
b7
are used to assign different functions to
the buttons.
Parameters
b11
...
b26
define the function of the four potential-free switching inputs E1 ... E4 and the two 230V AC inputs E5 and E6.
Input E3 is a special feature. It can be used to measure frequencies if it is set accordingly with
b33
.
Please note that the digital input or the frequency measurement is also available when the other option is set.
Due to the possibility of alternative front panel layouts, the position of the standard menu keys UP, DOWN and SET can be adjusted with
the parameters
b41
...
b43
.
Para-
meter
Functional description
Setting range
J1=0 J1=1
b 1
Special function Key T1 (if available)
0: Default
1: Burner reset
2: long press: SysOn/SysOff
3: Acknowledge
0
b 2
Special function Key T2 (if available)
see
b1
3
b 3
Special function Key T3 (if available)
see
b1
0
b 4
Special function Key T4 (if available)
see
b1
0
b 5
Special function Key T5 (if available)
see
b1
0
b 6
Special function Key T6 (if available)
see
b1
1
b 7
Special function Key T7 (if available)
see
b1
2
b11
Function external input E1 (potential-free)
0: Deactivated
1: Heater 1 On
2: reserved
3: Sensor oil release valve open
4: Heater 1 Alarm
5: filtration is being performed (either the valve for
manual operation, or feedback from the external Unit)
6: heating element on upper position
7: Overtemperature
8: Low Gas pressure
9: SysOn/Off
10: Recipe start
11: IR On/Off
12: Acknowledge
13: ECO request
14: Basket 1 at the device/up position
15: Basket 1 middle position
16: Basket 1 down position
17: Basket 2 at the device/up position
18: Basket 2 middle position
19: Basket 2 down position
0
b12
Function external input E2 (potential-free)
see
b11
0
b13
Function external input E3 (potential-free)
see
b11
0
b14
Function external input E4 (potential-free)
see
b11
0
b15
Function external input E5 (115 ... 230VAC)
see
b11
0
b16
Function external input E6 (115 ... 230VAC)
see
b11
0