Order number: 900318.002 V0.31
Page 19
© Störk-Tronic 2021 • www.stoerk-tronic.com • Subject to modifications.
Parameter tables
Para-
meter
Functional description
Setting range
J1 = 0 J1 = 1
H63
Sensor 2 select
1...6: F1 ... F6
2
H64
Mean weight
0.0 % (= Sensor 2)...100.0 % (= Sensor 1)
50.0
H65
Computed value
read-only
H66
VF2 = f(
H67
,
H68
,
H69
)
0: Deactivated
1: Average (VS21, VS22,
H69
)
2: Reserved
3: Reserved
4: Reserved
5: Difference ( VS21 – VS22 )
6: Amount | VS21 – VS22 |
0
H67
Sensor 1 select
1...6: F1 ... F6
1
H68
Sensor 2 select
1...6: F1 ... F6
2
H69
Mean weight
0.0 % (= Sensor 2)...100.0 % (= Sensor 1)
50.0
H70
Computed value
read-only
H71
VF3 = f(
H72
,
H73
,
H74
)
0: Deactivated
1: Average (VS31, VS32,
H74
)
2: Reserved
3: Reserved
4: Reserved
5: Difference ( VS31 – VS32 )
6: Amount | VS31 – VS32 |
H72
Sensor 1 select
1...6: F1 ... F6
1
H73
Sensor 2 select
1...6: F1 ... F6
2
H74
Mean weight
0.0 % (= Sensor 2)...100.0 % (= Sensor 1)
50.0
H75
Computed value
read-only
H76
VF4 = f(
H77
,
H78
,
H79
)
0: Deactivated
1: Average (VS41, VS42,
H74
)
2: Reserved
3: Reserved
4: Reserved
5: Difference ( VS41 – VS42 )
6: Amount | VS41 – VS42 |
0
H77
Sensor 1 select
1...6: F1 ... F6
1
H78
Sensor 2 select
1...6: F1 ... F6
2
H79
Mean weight
0.0 % (= Sensor 2)...100.0 % (= Sensor 1)
50.0
H99
Password level
H--
-99 ... 999
-19