Order number: 900318.002 V0.31
Page 18
© Störk-Tronic 2021 • www.stoerk-tronic.com • Subject to modifications.
Parameter tables
Para-
meter
Functional description
Setting range
J1 = 0 J1 = 1
H24
Software filter F3
1 ... 128
8
H25
Sensor value F4
H26
Offset correction F4
-99.0 K…99.0 K
0.0
H28
Sensor type F4
see
H18
0
H29
Software filter F4
1...128
8
H30
Sensor value F5
-
H31
The reference value for Sensor F5 at 4mA
-990.0 …
H32
[Unit
H33
]
0.0
H32
The reference value for Sensor F5 at 20mA
H31
… 990.0 [Unit
H33
]
100.0
H33
Sensor type F5
0: Sensor F05 disabled
1: Unit: 0.01 barg - relative
2: Unit: 0.01 bara - absolute
3: Unit: 0.1 °C
4: Unit: 0.1 %
5: Unit: 0.1 %rH
6: Unit: 0.1 µS
7: Unit: 0.1 cm
0
H34
Software filter F5
1 … 128
8
H35
Sensor value F6
-
H36
The reference value for Sensor F6 at 0V
-990.0 …
H37
[Unit
H38
]
0.0
H37
The reference value for Sensor F6 at 10V
H36
… 990.0 [Unit
H38
]
100.0
H38
Sensor type F6
see
H33
0
H39
Software filter F6
1…128
8
H40
Thermo compensation Sensor readout
---
H41
Mode thermocouple compensation
1: automatic with
H40
2: manual with
H42
1
H42
Manual thermocouple compensation Value
-300.0 ... 2999.9 °C
25.0
NTC Approximation
H50
Reference temperature 1: T_Ref 1
H57
…
H56
0.0
H51
Reference resistance 1: R_Ref 1
0.01kΩ … 500.00 kΩ (2 decimals)
30.902
H52
Reference temperature 2: T_Ref 2
H57
…
H56
20.0
H53
Reference resistance 2: R_Ref 2
0.001kΩ … 50.000 kΩ (3 decimals)
12.690
H54
Reference temperature 3: T_Ref 3
H57
…
H56
40.0
H55
Reference resistance 3: R_Ref 3
0.001kΩ … 50.000 kΩ (3 decimals)
5.715
H56
T_Max (exceeding yields sensor error message FxL)
H57
… 300.0 °C
50.0
H57
T_Min (undercutting yields sensor error message FxH)
-100.0 °C …
H56
0.0
Virtual Sensor
H60
Computed value
read-only
H61
VS1 = f(
H62
,
H63
,
H64
)
0: Deactivated
1: Average (VS11, VS12,
H64
)
2: Reserved
3: Reserved
4: Reserved
5: Difference ( VS11 – VS12 )
6: Amount | VS11 – VS12 |
0
H62
Sensor 1 select
1...6: F1 ... F6
1