Power Systems User's Guide Chapter 8: Preventative Maintenance
Chapter 8: Preventative Maintenance
Important note:
Please put the MC² Power System on a quarterly preventative maintenance schedule
to clean air intake filter(s). Failure to do so will void warranty.
Cleaning Procedures
When cleaning the MC² Power System, disconnect AC power source and separate
electronic enclosure and battery enclosure. Refer to “
Charger Timed-out Reset
Procedure
” for separation instructions. Use a damp (slightly wet), mildly soapy cloth to
clean the exterior of the power system. The following is a listing of approved cleaners
that are effective for cleaning the exterior of the power system:
•
Quaternary ammonium chloride compounds (such as AirX 109®)
•
Bleach – household strength (1:10 minimum dilution strength)
•
Ethyl or Isopropyl alcohol – 70%
•
Hydrogen
Peroxide
•
Phenolic Disinfectants (such as Lysol®)
•
WexCide®
•
Ovation®
•
Fantastic®
•
Formula
409®
•
1.6% Aqueous ammonia
•
“Green Soap” USP (United States Pharmacopoeia)
Cleaning the Filter Kit
The following instructions are recommended for cleaning the filter on the power system.
The filter kit is made up of three parts: finger guard, filter media, and retainer:
Finger Guard
Filter Media
Retainer
1110227 Revision 2
November 2006
33
Summary of Contents for MC2 POWER SYSTEMS
Page 1: ...MC2 Power Systems User s Guide November 2006 Document ID 1110227 Revision 2...
Page 12: ......
Page 40: ...MC2 Power Systems User s Guide 1110227 Revision 2 November 2006 28...
Page 44: ...Chapter 7 Troubleshooting MC2 Power Systems User s Guide 1110227 Revision 2 32 November 2006...
Page 50: ...Chapter 10 Battery Disposal 1110227 Revision 2 38 November 2006...
Page 54: ...Appendix B Mechanical Specifications 1110227 Revision 2 42 November 2006...
Page 56: ...Appendix C Power System Specifications 1110227 Revision 2 44 November 2006...