15
the air speed and the temperature difference in the house would increase enormously. As this may easily cause
a draught which would affect the animals the pressure control is switched off as soon as the hatches are open.
The inlet flaps, which were being controlled on the basis of pressure, are now temperature-controlled.
Humidification
This window enables you to switch the humidification control on or off and to set the relative humidity
percentage.
Temperature controls
The temperature control can both be adjusted as a heating or a cooling control. This can be a controlled or a
switched control, depending on the type of output.
Temperature control as heating
If temperature control has been set as heating, the temperature control is set identically to a heating, see page
13, with the exception of the minimum heating. This can be set separately here.
Temperature control as cooling
If temperature control has been set as cooling, the temperature control is set identically to the cooling on
page 14. Temperature setting: see page 8, Relative or absolute temperature setting.
Temperature monitoring
The temperature monitoring function is activated by
your installer.
The current measurement of each sensor is compared
with the measurement of one minute ago. Is the
temperature increase in that minute greater or equal
than the relative limits an alarm is given. If the
measurement is within the limits, the previous
measurement is made equal to the current
measurement and a new measurement is started.
Increases the temperature of the sensor above the
absolute limit, then there is also alarm.
The temperature monitor alarm occurs only when a
positive difference is detected (not when the
temperature drops down).
COMPENSATIONS CLIMATE CONTROL
Compensations ensure that the setting is increased
and/or decreased depending on:
with or without night settings;
the current outside temperature;
the current RH;
the current CO
2
level.
Wind speed and wind direction.
For RH and CO
2
correction, the largest value of
both corrections is decisive for the eventual
adjustment of the ventilation/flap position.
1 minute
Current measurement
Measurement of 1 minute ago
Temp. difference