The position switch should be mounted on an even surface. Please en-

sure that, even in case of failure, the position switch cannot be moved 

from its position. For protection against manipulation use oneway 

safety screws which are optionally available. 

When mounting actu-

ator and sensor, please observe the requirements of EN ISO 14119, 

especially paragraph 5.2 and 5.3!

 Please adjust screws at both sides 

with the same number of turns with a screwdriver. Please observe the 

instructions in the standards EN ISO 12100 and EN ISO 14120.

Application and Operation

=

DANGER

In case of overloaded contacts too high operation 

temperatures. 

Explosion hazard! Risk of burns! 

Ignoring this message will lead to serious injuries 

or death. For short-circuit protection use fuse size 

6 A (gG/gN).

-  Use device only within the permitted electrical load limits (see 

technical data).

-  Use device only within the permitted ambient temperature range (see 

product label and technical data)

Cleaning

=

DANGER

Live parts. 

Electric shock hazard! 

Ignoring this 

message will lead to serious injuries or death. 

Clean in accordance with protection class IP65.

-  Use a damp cloth to clean devices in explosive areas. This prevents 

electrostatic charge.

-  In case of damp cleaning: Use water or mild, non-scratching, 

non-chafing cleaners.

-  Do not use aggressive cleaners or solvents.

Maintenance / Service / Repair

=

DANGER

Live parts. 

Electric shock hazard! 

Ignoring this 

message will lead to serious injuries or death. 

Do not repair defective or damaged devices. Re-

place them.

=

DANGER

Explosive atmosphere. 

Explosion hazard! Risk of 

burns!

 Ignoring this message will lead to serious 

injuries or death. Do not rebuild or modify the de-

vice in any way.

With rough conditions, we recommend routine maintenance as follows:

1. Check actuator for easy operation.

2. Remove all dirt or particles.

3. Lubricate cam and roller shafts.

4. Check sealing of the cable or conduit connections.

Disposal

- Observe national, local and legal regulations concerning disposal.

-  Recycle each material separately.

Notices

Do not use the sensor as mechanical endstop. Any mounting posi-

tion is possible.

 

Furthermore, EN 60079-14 have to be applied for the 

installation of electrical equipment in explosive areas. Moreover, the 

ATEX test certificate and the enclosed special conditions have to be 

observed. The described products have been developed in order to 

assume safety functions as a part of an entire plant or machine. A 

complete safety system normally covers sensors, monitoring modules, 

indicator switches and concepts for safe disconnection. For the inte-

gration of the safety switch into the entire system, the control category 

determined in the risk assessment must be strictly observed and 

respected. Therefore, a validation according to DIN EN ISO 13849-2 or 

DIN EN 62061 is required. 

Furthermore, the Performance Level and 

SIL CL Level can be lower than the single level because of the combi-

nation of several safety components and other safety-related devices, 

e.g. by serial connection of sensors. 

The responsibility taken by the 

manufacturer of a plant or machine implies to secure the correct gen-

eral function. Subject to technical modifications. Moreover, steute does 

not assume any liability for recommendations made or implied by this 

description. From this description new claims for guarantee, warranty 

or liability cannot be derived beyond the general terms and conditions 

of delivery.

Summary of Contents for Ex 13 Series

Page 1: ...e IIC einen Abstand von 4 mm zwischen dem Bet tiger und umgebenden Metallfl chen sicher stellen Installation Montage Demontage GEFAHR Spannungsf hrende Teile und explosionsf hige At mosph re Stromschl...

Page 2: ...rious injuries or death Connecting and disconnecting only by qualified and authorised personnel Connecting and disconnecting only in non explosive environment Instandhaltung Wartung Reparatur GEFAHR S...

Page 3: ...s message will lead to serious injuries or death Do not repair defective or damaged devices Re place them DANGER Explosive atmosphere Explosion hazard Risk of burns Ignoring this message will lead to...

Page 4: ...lis dans le groupe de gaz IIC assurer une distance de 4 mm entre l actionneur et les parties m talliques environnantes Installation Montage D montage DANGER Pi ces sous tension et atmosph re explosive...

Page 5: ...re che il dispositivo sia stato installato correttamente Osservare le disposizio ni nazionali Fran ais Entretien Maintenance R paration DANGER Pi ces sous tension Risque d lectrocution Le non respect...

Page 6: ...detergenti o solventi aggressivi Manutenzione Riparazione Assistenza PERICOLO Componenti sotto tensione Pericolo di scossa elettrica Ignorare questo messaggio pu portare a gravi lesioni o morte Non t...

Page 7: ...l de 4 5 0 5 pF Para utilizar o dispositivo em grupo gasoso IIC deve haver uma dist ncia de 4 mm entre a bucha guia e as pe as de metal circun dantes Instala o Montagem Desmontagem PERIGO Partes vivas...

Page 8: ...namento de uso livre Na instala o de equipamentos operacio nais el tricos dever o ser atendidas observadas al m do acima cita do as determina es especifica es para reas sujeitas a riscos de explos o c...

Page 9: ...t de c blage Interrupteur de position Istruzioni di montaggio e di collegamento Interruttori di posizione Instru es de montagem e instala o Chaves fim de curso steute Schaltger te GmbH Co KG Br ckenst...

Page 10: ...acts Contacts Contatti Contatos Ex 13 1 1S Zb Die dargestellten Schaltsymbole beziehen sich auf den unbet tigten Zustand Contact symbols are shown for the not actuated switch Interrupteurs repr sent s...

Page 11: ...lation Switch type type 1 Coding level no coding Switching system slow action 1 NC 1 NO type Zb positive break NC contacts A Degree of protection IP 65 to IEC EN 60529 Termination 4 wire PVC cable H05...

Page 12: ...inforzata con fibre di vetro antiurto autoestinguente UL94 V0 iso lamento protettivo Tipo di interruttore tipo 1 Livello di codifica no codifica Sistema di commutazione commutazione lenta 1 NC 1 NA ti...

Page 13: ...R WH WHL WPH D DL Zulassung g ltig f r certificate valid for Ceritificat d essai est valide pour Omologazione valida per Aprova o v lida para Ex 13 1 1S W F KU WKU FKU R WR FR WH WHL WPH WHK D DL DS D...

Page 14: ...te of issue L hne June 24th 2008 nderung L hne 04 Oktober 2017 Revision L hne Oktober 04th 2017 Benannte Stelle der EG Baumusterpr fung Physikalisch Technische Bundesanstalt Notified Body of the EC ty...

Page 15: ...a na yczenie w j zyku polskim Op aanvraag kunt u deze montage en installatiehandleiding ook in uw taal verkrijgen Den h r monterings och elinstallationsinstruktionen finns ven till g nglig p ditt nati...

Page 16: ...tions de montage et de c blage Interrupteur de position Istruzioni di montaggio e di collegamento Interruttori di posizione Instru es de montagem e instala o Chaves fim de curso steute Schaltger te Gm...

Reviews: