SSD6000-SSD6000S-SE6000D4
18
Once the engine is running and all starting timers have expired, the animated icon is displayed.
It is possible to scroll to display the different pages of information by repeatedly operating the navigation
button.
Once selected the page will remain on the LCD display until the user selects a different page or after an
extended period of inactivity, the module will revert to the status display.
Engine Running
Failed to Start
Fault Finding
WARNING
- Please be aware of the potential hazards when working on a generator. Most basic fault finding
can be completed with ease. Other aspects of fault finding may require a trained technician to undertake to
ensure the safety to yourself and others.
Reference wiring diagram(s) in this handbook - The diagrams will correct as to the time of printing. Stephill
reserve the right to change the wiring diagrams without prior warning.
Starting Sequence
Once a start request is made the DSE 3110 will then attempt to crank the engine by operating the starter
motor and fuel relay.
When the engine fires, the starter motor is disengaged. (The DSE 3110 de-energises the starter motor relay
once it detects an output frequency (Hz) from the main alternator).
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest
duration after which the next start attempt is made.
Should this sequence continue beyond 3 attempts, the start sequence will be terminated and the LCD screen
will display;
Engine Running
Viewing the Instruments
Before Fault Finding
We strongly advise before attempting any fault finding is to check the health of the generator battery. It
should measure around 12.4 to 12.6 Volts DC while the generator is at standstill.
Be aware of the service/maintenance schedule of the engine, ensuring the fuel filters are replaced regularly
along with the oil topped up and oil filter etc. - See -
Service and Maintenance
Before carrying out any checks ensure all
Load
is unplugged from the generator and be aware of any
potential exposed
Live
terminals while the generator is running! All checks and tests should only be carried
out by a competent engineer.
Fig.15
above shows the page order when pressing the navigation button.