I N S T A L L A T I O N
Installation – step 2
Water supply installation
Water supply specification& quality:
Water supply pressure: 40 to 60PSI [2.8 to 4bar] – hammer free
Water supply temperature: 37 to 68°F [3 to 20°C]
ACA
Compressed air & water atomizing humidifier can accept a wide range of water quality.
Important
: the use of untreated water will lead to fine par cles deposit with the atomized
water, resul ng is fine powder deposit in surrounding surfaces or air filter.
ACA
should be connected to a clean, wholesome mains water supply. Installer and user are
responsible to ensure that the water supply system complies with local regula ons in regards
to Legionella and any other microbiological growth preven on,
A 1μm sediment filter and a silver ions an bacterial cartridge or UV sterilizer must be installed
on the water supply line.
Untreated water requirement
Pure water requirement
Water supply conduc vity: 1 to 156
µ
S/cm
Water supply TDS: 0 to 100 ppm TDS
Water supply PH: 6.5 to 7.5
Water supply chloride content: 0 to 50ppm
Water supply conduc vity: 0.1 to 0.5
µ
S/cm
Water supply TDS: 0.02 to 0.2 ppm TDS
Water supply PH: 6.5 to 7.5
Figure 6 – water supply connec on
13
2 stages filter (1μm)
+ silver ions (an bacterial)
or UV sterilizer
Shut off valve
(by others)