C O N F I G U R A T I O N & O P E R A T I O N
Programming mode
Steps Screen
Descrip on
Default password is 12345 Press enter
once value is entered
A
Press 1, for User mode
B
Enter desired Set point and press enter
C
You can select by pressing the down arrow
between:
‘’No’’ or ‘’with’’, then press enter
Pulses are recommended for smaller space
D
If With pulses is selected
enter the Pulse ON period in seconds
E
Enter then the Pulse OFF period in seconds
F
Air valve closing should be delayed by 10 to 20 seconds
a er water valves
this period can be adjusted depending on the water hose
length, longer the hose length is londer the delay should
be.
This delay can be set-up in the technician mode.
The Delay On should be set a 0sec, Delay Off will delay the
closing of the Air valve to the desired valu.
Once all se ngs have been entered, you should put the control panel off by switching
the main switch to Off for few seconds and put it back On
Once back On, press for few second on the bu on ‘’i’’ un l the ‘’SYSTEM’’ is
displayed.
Press enter
, then press le arrow
un l ‘’RESET’’ is displayed, press again enter
.
Controller will perform a reset. Once reset is complete, press on the right arrow 2
mes to verify that the se ng are recorded.
Make sure that the flip switch ‘’A/M”” located inside the control panel beside the control
terminal is on the ‘’A’’ posi on for Automa c
Operation mode
Once Control panel is ON, press on the ON/OFF green push bu on to put the ACA atomizing
humidifier on Automa c mode.
20