I N S T A L L A T I O N
Water supply connection:
1. Install a manual; shut off valve on the water main line.
2. If ACA distribu on panel is supplied with tap water it is recommended to install a 5µm
sediment filters on the line. This filter will protect internal water components from
clogging.
3. ACA atomizing humidifier is supplied with 2 stages filters 1
µ
m & an bacterial silver
ions cartridge. Install this pre-filter on the water main line downstream of the manual
shut-off valve.
4. Connect water supply to the 3/8in compression fi ng connec on. located at the
bo om of ACA distribu on panel and secure the water line.
5. Ensure that the water line is hammer free and leak free.
Important
: In case ACA atomizing humidifier is Off for more than 24hours, user should be
able to isolate the water main supply line and drain the ACA water supply line in order to
avoid any stagnant water and associated risk of legionella growth.
14