background image

6

OF  INCREASED  LEVELS  OF  CARBON  MONOXIDE  GAS 

IN  EXCESS  OF  SAFE  LIMITS  WHICH  COULD  RESULT  IN 

SERIOUS PERSONAL INJURY OR DEATH.

You should contact your gas supplier for any specific changes 

which may be required in your area.

As  elevation  above  sea  level  is  increased,  there  is  less 

oxygen  per  cubic  foot  of  air.    Therefore,  the  heater  input 

rate  should  be  reduced  at  high  altitudes  for  satisfactory 

operation with the reduced oxygen supply.  Failure to make 

this  reduction  would  result  in  an  overfiring  of  the  heater 

causing  sooting,  poor  combustion  and/or  unsatisfactory 

heater performance.

Ratings  specified  by  manufacturers  for  most  appliances 

apply for elevations up to 2000 feet (610m).  For elevations 

above 2000 feet (610), ratings must be reduced at the rate of 

4% for each 1000 feet (305m) above sea level.  For example, 

if a heater is rated at 120,000 Btuh (35 kWh) at sea level, 

to  rate  the  heater  at  4000  feet  (1219m),  you  subtract  4 

(once for each thousand feet) x .04 (4% input reduction) x 

120,000 (original rating) from the original rating.  Therefore, 

to  calculate  the  input  rating  at  4,000  feet  (121.9m):  4  x 

.04 x 120,000 =19,200 Btuh (5.6 kWh), 120,000 (35 kWh) 

-  19,200  (5.6  kWh)  =  100,800  Btuh  (29.4  kWh).    At  6000 

feet (1829m) the correct input rating should be 91,200 Btuh 

(26.7 kWh).

The  input  reduction  is  primarily  achieved  by  reducing  the  size 

of the main burner orifices.  To do this, the main burner orifices 

require replacement with orifices sized for the particular installation 

elevation.  Correct orifice sizing and parts may be obtained from 

State Water Heaters.  When ordering, be sure to state the model 

number and the altitude of the location where the water heater 

is being installed.

Upon  completion  of  derating  of  the  heater,  adjustment  to  the 

gas pressure regulator may be required.  See CHECKING THE 

INPUT  section  in  this  manual  for  inlet  and  manifold  pressure 

requirements.

Also due to the input rating reduction required at high altitudes, 

the  output  rating  of  the  appliance  is  reduced  and  should  be 

compensated for in the sizing of the equipment for application.

FEATURES

SELF-CLEANING HYDRO CANNON

These units include a self-cleaning hydro cannon installed 

in the front water inlet.  See figure 2.  The hydro cannon 

must be oriented correctly for proper function.  There is a 

marked range on the pipe nipple portion of the hydro cannon, 

that must be aligned with the top of the inlet spud.  A label 

above  the  jacket  hole  has  an  arrow  that  will  point  to  the 

marked portion of the pipe nipple if the orientation is correct. 

If the arrow does not point within the marked range on the 

pipe nipple, adjust the pipe nipple to correct. A pipe union is 

supplied with the hydro cannon to reduce the probability of 

misaligning the hydro cannon accidentally while tightening the 

connection to the inlet water supply line. Improper orientation 

of the hydro-canon can cause poor performance of the heater 

and can significantly reduce outlet water temperatures during 

heavy draws.

NOTE: The inlet tube may have 1, 3 or 7 cross-tubes.

FIGURE 2

For proper function, the hydro cannon must be oriented correctly.  

There is a marked range on the pipe nipple that must be aligned 

with the top of the inlet spud (check for label on the appliance) to 

assure proper orientation. Please check to confirm that the marked 

range is in alignment with the top of the spud.  A pipe union is 

supplied with the hydro cannon to help eliminate the possibility of 

changing the orientation by accidentally over-tightening the inlet 

supply line. Improper orientation of the hydro  cannon may cause 

temperature build-up issues or spells of colder than usual water 

temperatures.

HIGH LIMIT SWITCH

The digital thermostat (Fig. 3) contains the high limit (energy cutoff) 

sensor. The high limit switch interrupts main burner gas flow should 

the water temperature reach 203°F (95°C).

In the event of high limit switch operation, the appliance cannot be 

restarted unless the water temperature is reduced to approximately 

120°F (49°C). The high limit reset button on the front of the control 

then needs to be depressed.

Continued  manual  resetting  of  high  limit  control,  preceded  by 

higher  than  usual  water  temperature  is  evidence  of  high  limit 

switch operation. The following is a possible reason for high limit 

switch operation:

•  A malfunction in the thermostatic controls would allow the gas 

valve to remain open causing water temperature to exceed the 

thermostat setting. The water temperature would continue to 

rise until high limit switch operation.

Contact your dealer or service agent if continued high limit switch 

operation occurs.

DIGITAL THERMOSTAT

FIGURE 3

Summary of Contents for SBD100199*

Page 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Page 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Page 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Page 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Page 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Page 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Page 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Page 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Page 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Page 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Page 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Page 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Page 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Page 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Page 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Page 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Page 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Page 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Page 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Page 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Page 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Page 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Page 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Page 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Page 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Page 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Page 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Page 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Page 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Page 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Page 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Page 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Page 35: ...35...

Page 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Reviews: