background image

27

Valves for reducing point-of-use temperature by mixing cold and 

hot water are available.  Also available are inexpensive devices 

that attach to faucets to limit hot water temperatures.  Contact a 

licensed plumber or the local plumbing authority.

The water temperature is controlled by a thermostat, Fig. 3, which 

has two sensing elements.  One sensor is located near the top of 

the tank and the other is near the center.  The thermostat is set in 

the lowest position before the heater leaves the factory.

The  thermostat  temperature  dial,  Fig.  3,  is  accessible  by 

removing the control cover.  The dial is adjustable and may be 

set  for  120°F  (49°C)  to  180°F  (82°C)  water  temperature,  but 

120°F (49°C) is the recommended starting point.  It is suggested 

the  dial  be  placed  on  the  lowest  setting  which  produces  an 

acceptable  hot  water  supply.  This  will  always  give  the  most 

energy efficient operation.  The temperature control has a 4°F 

fixed differential.

TESTING DAMPER OPERATION

With the Service Switch in the AUTOMATIC OPERATION position, 

check the operation of the flue damper three (3) times with the 

water operating controls for proper operating sequence:

•  The damper disc must be open (in the vertical position) before 

the ignition and combustion process begins.

•  The damper disc must be in the open position when the main 

burner is firing.

•  The  gas  valve  must  close  and  the  main  burner  must  have 

ceased firing before the damper disc begins its return to the 

closed (horizontal) position.

If  during  testing  of  the  operation  of  the  damper  you  find  that 

there is a problem with the operation of the water heater when 

the Service Switch is in the AUTOMATIC OPERATION position: 

 

Reset the Service Switch to the HOLD OPEN DAMPER position 

and check operation again.

If the water heater does operate when placed in the HOLD OPEN 

DAMPER position:

•  Refer  to  the  EFFIKAL  RVGP-FSF-SERIES  TROUBLE-

SHOOTING GUIDE at the end of this manual.

 CAUTION

Do not force the damper disc manually or motor damage will 

occur.

If the water heater does not operate with the Service Switch in 

either position:

•  Refer  to  the  Troubleshooting  Sections  and  Operational

 

Checklist sections.

CHECKING VENTING

The  following  steps  shall  be  followed  with  each  appliance

 

connected to the venting system placed in operation, while any 

other  appliances  connected  to  the  venting  system  are  not  in 

operation.

ADJUSTMENTS

ON INITIAL STARTUP SOME ADJUSTMENTS ARE NECESSARY.

.  CHECK MANIFOLD AND INLET GAS PRESSURES.

2.  TO ADJUST  PILOT  FLAME  -  FOLLOW  “PILOT  BURNER”      

PROCEDURE UNDER “PREVENTIVE MAINTENANCE”.

WATER TEMPERATURE CONTROL

 WARNING

THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE 

THERMOSTAT TO CONTROL WATER TEMPERATURE.  HOT 

WATER  TEMPERATURES  REQUIRED  FOR AUTOMATIC 

DISHWASHER AND  LAUNDRY  USE  CAN  CAUSE  SCALD 

BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/OR 

DEATH.  THE TEMPERATURE AT WHICH INJURY OCCURS 

VARIES WITH THE PERSON’S AGE AND TIME OF EXPOSURE.  

THE  SLOWER  RESPONSE TIME  OF  CHILDREN, AGED  OR 

DISABLED PERSONS INCREASES THE HAZARDS TO THEM.  

NEVER ALLOW  SMALL  CHILDREN TO  USE A  HOT  WATER 

TAP, OR DRAW THEIR OWN BATH WATER.  NEVER LEAVE A 

CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB 

OR SHOWER.

THE  WATER  HEATER  SHOULD  BE  LOCATED  IN AN AREA 

WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS 

TO SET TEMPERATURES.

SETTING THE WATER HEATER TEMPERATURE AT 120°F WILL 

REDUCE THE RISK OF SCALDS.

  Some states or provinces 

require settings at specific lower temperatures.

Below you will find listed the approximate time-of-burn relationship 

for normal adult skin.  Short repeated heating cycles caused by 

small hot water uses can cause temperatures at the point of use 

to exceed the thermostat setting by up to 20°F (11°C).

If you experience this type of use, you should consider using lower 

temperature settings to reduce scald hazards.

 

Temperature 

Time to Produce 2nd & 3rd

 

Settings 

Degree Burns on Adult Skin

 

180°F (82°C) 

  Nearly Instantaneous

 

170°F (77°C) 

  Nearly Instantaneous

 

160°F (71°C) 

  About 1/2 Second

 

150°F (65°C) 

  About 1 - 1/2 Seconds

 

140°F (60°C) 

  Less than 5 Seconds

 

130°F (54°C) 

  About 30 Seconds

 

120°F (49°C) 

  More than 5 Minutes

Summary of Contents for SBD100199*

Page 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Page 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Page 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Page 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Page 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Page 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Page 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Page 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Page 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Page 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Page 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Page 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Page 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Page 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Page 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Page 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Page 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Page 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Page 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Page 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Page 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Page 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Page 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Page 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Page 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Page 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Page 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Page 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Page 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Page 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Page 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Page 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Page 35: ...35...

Page 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Reviews: