17
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 27. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE
WITH RECIRCULATION OF SANITIZING LOOP
NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER
CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING
MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON)
DURING THE RINSE OPERATION AND OPEN (OFF) WHEN
DISHWASHER IS NOT OPERATING OR WHEN ON LONG
STANDBY.
NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN
UNINSULATED TEE BEYOND THE DISHWASHING MACHINE
TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD
BE SET AT 185°F (85°C).
NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW
RATE DOES NOT CAUSE UNNECESSARY TURBULENCE
IN THE TANK.
* TEMPERED WATER LOOP, IF USED, CONNECT TO
POINT “A”.
**PIPE RELIEF VALVE TO OPEN DRAIN.
INSTALL IN ACCORDANCE WITH LOCAL CODES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW
PREVENTER, CHECK VALVE OR WATER METER WITH
CHECK VALVE. PROVISIONS FOR THERMAL EXPANSION
OF WATER IN THE HOT WATER SYSTEM MUST BE
PROVIDED.