background image

28

1.  Seal any unused openings in the venting system.

2.  Inspect the venting system for proper size and horizontal pitch, 

as required in the National Fuel Gas Code, ANSI Z223.1 and 

these  instructions.  Determine  that  there  is  no  blockage  or 

restriction,  leakage,  corrosion  and  other  deficiencies  which 

could cause an unsafe condition.

3.  So far as is practical, close all building doors and windows and all 

doors between the space in which the water heater(s) connected 

to the venting system are located and other spaces of the building. 

Turn on all appliances not connected to the venting system. Turn on 

all exhaust fans, such as range hoods and bathroom exhausts, so 

they shall operate at maximum speed. Close fireplace dampers.

4.  Follow the lighting instruction.  Place the water heater being 

inspected in operation.  Adjust thermostat so appliance shall 

operate continuously.

5.  Test for draft hood spillage at the relief opening after 5 minutes 

of main burner operation.

6.  After it has been determined that each appliance connected 

to the venting system properly vents when tested as outlined 

above, return doors, windows, exhaust fans, fireplace dampers 

and any other gas burning appliance to their previous conditions 

of use.

7.  If improper venting is observed during any of the above tests, 

the venting system must be corrected.

 WARNING

FAILURE  TO  CORRECT  BACK  DRAFTS  MAY  CAUSE AIR 

CONTAMINATION AND UNSAFE CONDITIONS.

•   If the back draft cannot be corrected by the normal method or 

if a suitable draft cannot be obtained, a blower type flue gas 

exhauster  must  be  employed  to  assure  proper  venting  and 

correct combustion.

PREVENTIVE MAINTENANCE

CHECK THE PILOT

At least once a year, check the pilot burner, fig. 14, and the main 

burner, fig. 15, for proper operation.  Refer to the following pilot 

and main burner sections.

PILOT BURNER

For  access  to  pilot,  unfasten  two  screws  to  burner  cover  and 

remove.  Locate the burner with pilot and remove screw holding 

burner to manifold.  Unfasten pilot tubing from valve and slide out 

burner and pilot.

Servicing of the pilot burner includes  keeping  pilot free of lint, 

cleaning the burner head, the primary air opening and the orifice 

of the pilot burner.

Pilot burner flame is affected by:

1.  Low gas pressure.

  •  Adjust  pilot  flame  by  means  of  the  pilot  gas  adjustment 

located on the gas valve.  See fig. 16.

  •  The  pilot  flame  should  envelop  sensing  device  with  5/8”

 

(1.6cm)  flame,  fig.  15.    Remove  pilot  adjustment  cover 

screw, fig. 16.  Turn inner adjustment screw clockwise to 

decrease, or counterclockwise to increase pilot flame.  Be 

sure to replace cover screw on gas valve after adjustment 

to prevent possible gas leakage.

2.  Clogged pilot burner orifice.

  •   Clean or replace orifice.  A clogged orifice will restrict gas 

flow.

3.  Incorrect orifice.

  •  Replace.  See Table 7, for correct orifice for type of gas used.  

Orifice size is stamped on the wrench flats.

FIGURE 13

Pilot sensing device must sense a flame before sparking will stop.  

Loose wires or a draft may cause intermittent or abnormal sparking.  

To eliminate this condition, first correct loose wiring condition, and 

then, if necessary, increase pilot flame.

PILOT BURNER ASSEMBLY

FIGURE 14

MAIN BURNER

The  main  burner,  fig.  15,  should  display  the  following 

characteristics:

•    Cause  rapid  ignition  and  carry  over  of  flame  across  entire

 

burner.

•  Give reasonably quiet operation during ignition, burning and

    

extinction.

•  Cause no excessive lifting of flame from burner ports.

Summary of Contents for SBD100199*

Page 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Page 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Page 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Page 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Page 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Page 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Page 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Page 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Page 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Page 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Page 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Page 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Page 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Page 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Page 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Page 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Page 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Page 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Page 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Page 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Page 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Page 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Page 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Page 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Page 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Page 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Page 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Page 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Page 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Page 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Page 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Page 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Page 35: ...35...

Page 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Reviews: