Control Panel Installation
53722
4-33
4.13.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A at the back of
this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-32.
2. Configure the circuit for Class A in programming (see Section 9.5).
Figure 4-32 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-32 uses both Flexput circuit 1 and 2, so in programming it
would be referred to as point 1.
Maximum voltage drop is 3V per Class A circuit. See Table 4-4
Table 4-4: Maximum Impedance Class A
Current
Maximum Impedance
1.0A
3
Ω
1.5A
2
Ω
2.0A
1.5
Ω
2.5A
1.2
Ω
3.0A
1.0
Ω
Supervised
Power Limited
Regulated 24 VDC
3A per Circuit, 9A max Combined
Summary of Contents for SCSS-700
Page 2: ......
Page 12: ...SCSS 700 Installation Manual 8...
Page 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Page 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Page 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Page 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Page 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Page 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Page 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Page 250: ...SCSS 700 Installation Manual A 14 53722...
Page 254: ...Cut Along the Dotted Line...
Page 256: ......
Page 257: ......