10.7.2 Double Interlock Zone Releasing
A Double Interlock Zone uses a minimum of two Addressable detectors, a designated manual
release switch, and an interlock switch input. An interlock switch is typically a dry-contact
pressure switch and will be referred to as an interlock/pressure switch in this document.
Conditions Required for a Pre-Alert Output Activation
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts
the user that the initial stages required for a release condition are present. (Also refer to Table
10-3.)
Conditions Required for a General Alarm Output Activation
If two addressable detectors, a manual release switch is activated, or an interlock switch is
active, the "Pre-Alert", and "General Alarm" outputs will activate.
Conditions Required for a Release Output Activation
Any release requires the activation of an interlock switch, and either a manual release switch
or 2 activated addressable detectors. When these conditions are met, the “Release” and
“General Alarm” outputs will activate, and the “Alert” outputs will deactivate.
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Each Double Interlock Zone input requires at least one Interlock/pressure switch
Table 10-4: Double Interlock Zone Operation
Inputs
Output Results
1st Addressable Detector
4
4
4
2nd Addressable Detector
4
4
4
Manual Release Station
4
4
4
4
Interlock/Pressure Switch
4
4
4
4
4
Nor
m
al
Pr
e-Alert
Pr
e-Alert
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Pre-Alert an
d Ge
ne
ral
A
la
rm
Relea
se an
d Ge
ner
a
l
Alar
m
Relea
se an
d Ge
ner
a
l
Alar
m
Relea
se an
d Ge
ner
a
l
Alar
m
Relea
se an
d Ge
ner
a
l
Alar
m
Relea
se an
d Ge
ner
a
l
Alar
m
Summary of Contents for SCSS-700
Page 2: ......
Page 12: ...SCSS 700 Installation Manual 8...
Page 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Page 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Page 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Page 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Page 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Page 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Page 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Page 250: ...SCSS 700 Installation Manual A 14 53722...
Page 254: ...Cut Along the Dotted Line...
Page 256: ......
Page 257: ......