9.6.5.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction
with a water flow switch. The delay is system-wide. All water flow switches on the system
will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select for Panel Programming.
Display reads:
Initializing
Please wait . . .
3. Select for System Options.
4. Select for Miscellaneous Options 1.
A screen similar to the one shown in Figure 9-11 will display.
Figure 9-11 Water Flow Delay Programming Screen
5. Enter the number of seconds (0 to 90) to delay a water flow switch alarm, then press
.
Delay in seconds before waterflow
alarm occurs (00-90)