Model SCSS-700 Installation Manual
3-14
53722
U
Select holiday schedule (up to 18 days) if installation is using day/night sensitivity.
U
Set up reporting accounts.
U
Select options for phone lines.
U
Customize banner message (message that displays on LCD in normal mode) if
desired.
Input Point (SLC Device) Configuration
JumpStart AutoProgramming automatically selects some options for SLC devices (see “JumpStart
AutoProgramming” section of this chart). You can change options selected by JumpStart AutoProgramming, if
necessary and further customize input point options.
U
Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart
AutoProgramming assigns all switches as Manual Pull type.)
U
If the installation includes duct detectors, program detector type. (JumpStart
AutoProgramming does not distinguish duct detectors from ordinary smoke
detectors.)
U
Assign a name (or description) to the point.
U
Assign input points to zones, if necessary. (JumpStart AutoProgramming assigns all
input points to Zone 1.)
Zone Configuration
U
Add the zone to the system if it does not already exist.
U
Program a name (or description) for the zone.
U
Select alarm delay options (detection characteristics) for zone.
U
Select heat detector trip temperature and/or smoke sensitivity level for photoelectric
smoke detectors.
Output Point Configuration
Conventional notification circuits (circuits 1-8):
U
Enable circuits used for notification appliances through programming, if necessary.
Conventional relay circuits (circuits 9-10):
U
Select options for relay circuits, if desired. Note: Relay circuits will always output
continuously (constant pattern), even if assigned to an Output Group that uses a
different output pattern.
Auxiliary power circuits (circuits 1-8):
U
Enable any circuit used for auxiliary power devices through programming.
U
Select type of power (door holder, constant, or resettable)
Addressable relay modules
U
Assign addressable relay modules to output groups through programming.
(JumpStart AutoProgramming assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
U
Assign LED modules to output groups through programming.
All output circuits (1-8):
U
Disable (set to UNUSED) any unused circuits. If you do not disable unused output
circuits, they will cause a trouble condition (unless an EOL resistor is used).
U
Select a name for the point, if desired.
Output Group Configuration
U
Add the group to the system if it does not already exist.
Task
See Section
(for more info.)
Summary of Contents for SCSS-700
Page 2: ......
Page 12: ...SCSS 700 Installation Manual 8...
Page 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Page 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Page 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Page 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Page 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Page 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Page 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Page 250: ...SCSS 700 Installation Manual A 14 53722...
Page 254: ...Cut Along the Dotted Line...
Page 256: ......
Page 257: ......