Operation
30
266665 / 640960300140
2018-11-09·BA00·III·en·00
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Emergency Luminaire with LED
Series EXLUX 6409/4
During power supply operation
Blinking: 1 second on, 1 second off
Flashing: 0.25 seconds on, 0.75 seconds off
During emergeny light operation
The LED indicator is switched off.
10.4 Troubleshooting
Refer to the following troubleshooting chart during troubleshooting:
The LED indicator lights up in green after troubleshooting.
Green
Luminaire is ready
for operation
Flashing green
Luminaire is ready
for operation
Function and rated operating time test activated
Red
Error
Battery is defective or electric circuit is interrupted
Flashing red
Error
Last function and/or rated operating time test faulty
Flashing red
Error
LEDs defective
Flashing
green/red
Luminaire is ready
for operation, no emergency
light operation
Emergency light operation is deactivated by
remote switch
Flashing
green/red
Luminaire is ready
for operation
Reset signal detected
Cause of error
Troubleshooting
The LEDs are defective.
Replace the mounting plate including LED
and the control gear.
The control gear is defective.
Replace the mounting plate including
LEDs and the control gear.
The switch is defective.
Replace the switch.
Red LED indicator
The battery is defective.
Replace the battery.
The switch in the battery box is defective. Replace the switch.
The switch in the luminaire is defective.
Replace the switch.
LED indicator blinking red
The battery capacity is too low.
Replace the battery.
The LEDs are defective.
Replace the mounting plate including LED
and the control gear.