Emergency Luminaire with LED
Series EXLUX 6409/4
Opening and closing the battery case
8.3.2 Electrical connections
Electrical connection
Observe the maximum clamping possibility of the connecting terminals
(see chapter "Technical data").
For optional screw terminals, two conductors per clamping unit can be clamped
(ingoing and outgoing wiring).
Observe the following when connecting to the main supply:
• Clamping must be carried out precisely!
• Do not clamp any part of the conductor insulation!
• Do not interchange the conductors!
• Observe the technical regulations when connecting the conductor!
• Clamp the conductor firmly.
• Do not remove the terminal cover of optional screw terminals to clamp the conductor!
• The phase L1 must be directly connected to the grid which functions as charging
phase for the battery!
• Optional screw terminals: Firmly tighten screws (tightening torque 2 Nm,
for unused clamping units 0.7 Nm)!
16404E00
16405E00
Opening:
• Loosen the screws (1)
(cross head H2).
• Open the battery cover (2).
Closing:
• Close the battery cover (2).
• Tighten the screws (1)
(cross head H2) firmly (2 Nm).
NOTICE
Danger due to wrong connection.
Malfunction
• Phases L and L1 must be connected in phase.
1
2
1
2