Emergency Luminaire with LED
Series EXLUX 6409/4
• Remove the battery plug from the chamber.
• Disconnect the battery plug (4).
• Take off the battery cover with installed battery (5).
• Put on and secure the battery cover with installed battery (5).
• Connect the battery plug (4).
• Loosen the strap (3) from the wrist and store it in the battery case.
• Close the battery case and ensure that the conductors do not get jammed.
• Tighten the screws (1) (cross head H2) firmly (2 Nm).
Resetting the error indication "blinking red" after replacing the battery
16406E00
The error indication "blinking red" remains active after successfully replacing
the battery.
Deactivation:
Automatic:
• After replacing the battery a rated operating time test is carried out
automatically within 14 days.
• The error will be reset once this test has been passed successfully.
Manual:
• The line voltage must be switched on.
• Actuate the switch in the battery case for 5 seconds.
• Release the switch.
• Actuate the switch twice within 10 seconds for a duration of 2 seconds.
• Resetting of the error will be shown on the LED indicator for 5 seconds
by blinking red/green.
• The error is reset.
• Close the battery case.