background image

Operation

26

251986 / 6118602300

2019-03-07·BA00·III·en·03

EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN

Compact Sheet-steel 

Emergency Light Fitting

Series 6118/1

10.2 Indications

When connecting to the power supply

Initialisation within 30 seconds

After that, the LED display switches to the operating mode.

During normal operation

Blinking: 1 second on, 1 second off

Flashing: 0.25 seconds on, 0.75 seconds off

During emergeny light operation

The LED display is switched off.

10.3 Troubleshooting

Observe the following troubleshooting plan for troubleshooting:

Second Description
0 to 10 Function test green LED
10 to 20 Function test red LED
20 to 30 continuous operation 

test state

green LED blinks - continuous operation test active
red LED blinks - continuous operation test not active

Green

Light fitting is ready for  

operation

blinking 

green

Light fitting is ready for  

operation

Function or continuous operation test is  

activated

Red

Error

Battery is defective or electric circuit is  

interrupted

blinking red Error

Battery capacity is too low

flashing red Error

The lamp reached its end of service life or is 

defective

blinking  

green/red

Light fitting is ready for  

operation No emergency 

light operation

Emergency light operation is deactivated by 

remote switch

Cause of error

Troubleshooting

The lamp was incorrectly inserted.

Insert the lamp correctly.

The lamp is defective.

Replace the lamp.

The ballast is defective.

Replace the ballast.

The switch is defective.

Replace the switch.

The lamp reached its end of service life.

Replace the lamp.

LED display red
The battery is defective.

Replace the battery.

The switch in the battery case is defective. Replace the switch.
The switch in the light fitting is defective.

Replace the switch.

LED display blinking red
The battery capacity is too low.

Replace the battery.

Summary of Contents for 6118/1 Series

Page 1: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages r stahl com EN Compact Sheet steel Emergency Light Fitting Series 6118 1...

Page 2: ...2 Safe use 5 3 3 Intended Use 5 3 4 Modifications and alterations 6 4 Function and device design 6 4 1 Function 6 4 2 Device design 7 5 Technical data 7 6 Engineering 10 6 1 Mains operation 10 6 2 Eme...

Page 3: ...ates and EU Declaration of Conformity r stahl com The device has IECEx approval For certificate please refer to the IECEx homepage http iecex iec ch Further national certificates can be downloaded via...

Page 4: ...ICE Type and source of danger damage Consequences of danger Taking countermeasures to avoid the danger or damage Symbol Meaning Tips and recommendations on the use of the device Danger due to explosiv...

Page 5: ...ion Observe national assembly and installation regulations e g IEC EN 60079 14 Observe national safety and accident prevention regulations During installation and operation observe the information cha...

Page 6: ...nd closed remote switch the light fitting switches to emergency light operation and the lamp is supplied with voltage and power for a set period of time via the integrated battery The light fitting au...

Page 7: ...a 18248E00 1 Cable gland 6 Luminaire enclosure 2 Glass pane 7 Seal 3 Reflector plate 8 Lamp holder 4 Ballast 9 Central lock 5 Battery 10 Stopping plug Explosion Protection Global IECEx Gas and dust IE...

Page 8: ...losure Sheet steel powder coated white similar to RAL 9016 Stainless steel SS316L V4A 1 4404 brushed Lens Safety glass Seal Foamed silicone seal in luminaire enclosure Luminaire locking Central lockin...

Page 9: ...oth sides of the luminaire for mounting of wall mounting brackets Recessed light fitting Variant 1 mounting frame attached to enclosure using M6 screws Variant 2 mounting frame welded to enclosure Not...

Page 10: ...y Light Fitting Series 6118 1 6 Engineering 6 1 Mains operation 6 1 1 Stand by operation The light fitting is switched off 6 1 2 Continuous operation The light fitting is switched on 6 1 3 Normal ligh...

Page 11: ...6043 7 The following connection versions are possible Point to point connection Linear connection 16400E00 Remote switch is closed Remote switch is opened Power supply operation Switching on the lamps...

Page 12: ...materials Handle with care Store protected from fire sources of dust harmful gases and liquids Store in a dry and cool location Recommendation Store battery at an ambient temperature of 5 to 25 C and...

Page 13: ...s not affected due to external influences i e pressure conditions chemical mechanical thermal and electric impact such as vibration humidity and corrosion see IEC EN 60079 14 The device must only be i...

Page 14: ...out with fastening set for wall and ceiling mounting A Insert nut sealed with blind plug Dimensional drawings All dimensions in mm inches Subject to modifications 521 20 51 25 0 98 6 x 10 6 x 0 39 65...

Page 15: ...es DANGER Explosion hazard due to inadmissible heating Non compliance results in severe or fatal injuries Avoid external heat sources and or direct sunlight risk of change of temperature class or chan...

Page 16: ...teel Emergency Light Fitting Series 6118 1 8 2 1 Frame mounitng 8 2 2 Mounting bracket Example Assembly of mounting bracket All other brackets are mounted as shown in the example 17247E00 Mount the fr...

Page 17: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Compact Sheet steel Emergency Light Fitting Series 6118 1 8 2 3 Ring Bolt Assembly 18291E00 Screw the 2 ring eyes into the mounting part Attach the mounti...

Page 18: ...results in severe or fatal injuries Open luminaires without switch only in de energized state see information plate on the lock 18242E00 18245E00 18244E00 Remove the closing cap 11 of the central loc...

Page 19: ...st being switched on again Version with switch The luminaire is positively disconnected from the power supply by actuating the central lock In open end position and with translucent cover swivelled do...

Page 20: ...carried out precisely Do not clamp any part of the conductor insulation Do not interchange the conductors Observe the technical regulations when connecting the conductor Clamp the conductor firmly Do...

Page 21: ...ngth 10 11 mm 16333E00 16408E00 The connection to the battery is interrupted Before commissioning connect the battery NOTICE Deep battery discharge due to non utilisation Non compliance may lead to ma...

Page 22: ...lowing the required dust resistance the required type of protection the required temperature resistance the IP degree of protection according to the rating plate the operating instructions of the cabl...

Page 23: ...g plugs have been tightened firmly Check if all conductors have been clamped firmly Check if the line voltage and the rated operational voltage are consistent Check if the permissible conductor diamet...

Page 24: ...e operation mode of the selected emergency light operating time Emergency light operation time Stand by operation The lamp is switched off regardless of normal lighting Continuous operation The lamp i...

Page 25: ...of the lamps and the battery Continuous operation test starts within 44 days after commissioning is carried out every 365 days discharges the battery up to the final discharge voltage checks the func...

Page 26: ...Light fitting is ready for operation blinking green Light fitting is ready for operation Function or continuous operation test is activated Red Error Battery is defective or electric circuit is interr...

Page 27: ...e cracks or other visible signs of damage the seals for ageing and damage the device inside and outside for pollution and clean it if neccessary compliance with the permissible temperatures according...

Page 28: ...ff the lamp at the end of the service life CAUTION Danger of electric shock due to energised parts Non compliance can result in minor injuries All connections must be disconnected from the power suppl...

Page 29: ...the form and send it Confirmation will be sent R STAHL s customer service will contact you You will receive an RMA form after speaking with customer service Send the device along with the RMA form in...

Page 30: ...are parts CAUTION Danger due to chemical reactions Human health and the environment are at risk Batteries collect them separately dispose of them in controlled fashion do not dispose of them in the do...

Page 31: ......

Reviews: