Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
Emergency light blocking
A remote switch for emergency light blocking can be connected to terminals 9 and 10 of
the emergency light electronics.
10.1.2 Function and capacity test
To carry out the test, the following prerequisites must be fulfilled:
• The time interval has expired.
• The power supply operation was active for at least 1 hour.
• The remote switch is closed.
The test result is shown on the LED display.
During a test the lamps are switched on.
Function test
• starts within 24 hours after commissioning.
• is carried out every 7 days.
• takes 1 minute.
• checks the function of the lamps and the battery.
Continuous operation test
• starts within 44 days after commissioning.
• is carried out every 365 days.
• discharges the battery up to the final discharge voltage.
• checks the function of the lamps and the capacity of the battery.
• can be deactivated and activated.
Deactivating and activating the continuous operation test:
• switch of the supply voltage.
• switch on the supply voltage.
• within 60 seconds, switch the lamps on and off 3 times for 5 seconds each.
The result will be shown on the LED display for 30 seconds.
16400E00
Remote switch is closed
Remote switch is opened
Power supply
operation
Switching on the lamp depending
on operation mode
Switching on the lamp depending
on operation mode
Power failure
Emergency light function
No emergency light function
14
13
12
11
10
9
8
F
LED green
LED grün
LED red
LED rot
mit Brücke
ohne Brücke
with jumper
without jumper
3 h
1,5 h
BAT-
BAT+
Fernschalter
Remote switch
Fernschalter
Remote switch