Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
Technical Data
Electrical data
Ballast
Inrush current
Power factor cos
p
)
0.95
Ambient conditions
Operating
temperature range
Storage temperature - 25 °C ... + 55 °C
Mechanical data
Degree of protection IP65
IP64 when using 8162 breather
IP66 when using mounting or cover frame
(IEC 60598)
Protection class
I
(with internal PE-terminal)
Impact strength
(IK code)
IK10 (IEC 62262)
Material
Enclosure
Sheet-steel, powder-coated, white, similar to RAL 9016
Stainless steel SS316L (V4A | 1.4404) brushed
Lens
Safety glass
Seal
Foamed silicone seal in luminaire enclosure
Luminaire locking Central locking; glass cover hinged for access
6118/1...-....-.6..-....
6118/1...-....-.7..-....
Quantity EB
1
1
Lamp start
Cold start
Cold start
Voltage
110 ... 127 V ± 10 % AC 220 ... 240 V ± 10 % AC
Frequency
50 ... 60 Hz
50 ... 60 Hz
Lamp standard
IEC 60081
IEC 60081
Lamp power
1 x 8 W
1 x 8 W
Nominal current
93 mA ± 10 % at 120 V
45 mA ± 10 % at 230 V
6118/1...-....-.6..-....
6118/1...-....-.7..-....
I
peak
15.5 A
32.4 A
Δt
126
m
s
130
m
s
maximum number of luminaires per miniature circuit breaker:
6118/1...-....-.6..-....
at 120 V
6118/1...-....-.7..-....
at 230 V
Type
10 A
16 A
20 A
10 A
16 A
20 A
B
27
44
55
13
20
25
C
46
73
92
21
34
42
- 20 °C ... + 50 °C
- 5 °C ... + 50 °C
optimal ambient temperature for the battery