Mounting and installation
21
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
Connection terminals
Battery connection
Standard:Spring clamp
terminals up to 4 mm
2
Optional:
Screw-type terminals
up to 4 mm
2
finely and
extra finely stranded,
and 6 mm
2
solid
Stripping length:
10 ... 11 mm
Stripping length:
10 ... 11 mm
16333E00
16408E00
The connection to the battery is interrupted.
Before commissioning, connect the battery.
NOTICE
Deep battery discharge due to non-utilisation.
Non-compliance may lead to material damage!
• If the luminaire is not connected to the power supply for more than 4 weeks the
battery must be disconnected.
18458E00
• Disconnect the conductor from the terminal
(I).
• Connect the conductor to terminal 8 of the
emergency light electronics.
• Tighten the screw of the terminal
with 1.2 Nm.
L1
N
L'
L2
L3
L‘
= switched phase
L1
= charging phase
L2, L3
= phase
N
= neutral conductor
PE
= protective conductor
I
8
9
10
11
12
13
14