Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
8.3.3 Cable entries
The standard luminaire is delivered with 3 lead-in holes, 2 cable glands and 2 stopping
plug.
Tightening torques for components from R. STAHL Schaltgeräte GmbH
Luminaires with installed cable entries and stopping plugs from
R. STAHL Schaltgeräte GmbH must be tightened using the following values:
Luminaires with approved cable entries and stopping plugs; not supplied by
R. STAHL Schaltgeräte GmbH
Please observe the following:
• the required dust resistance!
• the required type of protection!
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable entries and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
Tightening torque
Connection thread
Pressure screw
Cable entry
8161
M20 x 1.5
2.3 Nm
1.5 Nm
M25 x 1.5
3.0 Nm
2.0 Nm
Stopping plugs
8290
M20 x 1.5
1.0 Nm
–
M25 x 1.5
1.5 Nm
–
DANGER
Explosion hazard due to impermissible cable entries and stopping plugs!
Non-compliance results in severe or fatal injuries.
• Only use separately certified cable glands and stopping plugs which
have been tested and certified according to Directive 2014/34/EU
(ATEX) or IECEx (CoC) and which comply with the standard version
stated in the certificate of the luminaire.