251986 / 6118602300
2019-03-07·BA00·III·en·03
Mounting and installation
15
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
8.2
Mounting / dismounting, operating position
DANGER
Explosion hazard due to electrostatic discharge!
Non-compliance results in severe or fatal injuries.
Do not use of the luminaire in strong charge generating environments!
The following processes/activities should be avoided:
• pneumatic conveyance of dust
• spraying of electrons
• fast-rotating brushes
DANGER
Explosion hazard due to inadmissible heating!
Non-compliance results in severe or fatal injuries.
• Avoid external heat sources and/or direct sunlight (risk of change of
temperature class or change of maximum permissible surface
temperature).
• Do not exceed the maximum ambient temperature due to external heat
sources (premature failure of equipment).
The luminaire is suitable for wall and ceiling mounting.
Wall mounting must be performed with the central lock directed downwards.
The mounting position with light emission upwards is not allowed when
mounted outdoors.
For outdoor use, we recommend to install a 8162/1 breather from
R. STAHL Schaltgeräte GmbH.
The breather guarantees compliance with degree of protection IP64 in all
mounting positions.