FirstLine UPS
Form No. 003-2323 Rev B
14
Table 6-FirstLine UPS 25-37.5 kVA Current Requirements
UPS
Rating
Input
Voltage
Input
Transformer
Option
Max. Input
Current (A)
Allowed for
Specified
Branch
Protector
Maximum
Allowable Branch
Circuit Protection
(A)
25 kVA
208 V None
80
100
25 kVA
208 V Isolation
80
100
25 kVA
220 V None
80
100
25 kVA
480 V Standard auto
40
50
25 kVA
480 V Isolation
40
50
30 kVA
208 V None
100
125
30 kVA
208 V Isolation
100
125
30 kVA
220 V None
100
125
30 kVA
480 V Standard auto
48
60
30 kVA
480 V Isolation
48
60
37 kVA
208 V None
120
150
37 kVA
208 V Isolation
120
150
37 kVA
220 V None
120
150
37 kVA
480 V Standard auto
60
75
37 kVA
480 V Isolation
60
75
UPS
Rating
Output
Voltage
Rated Max.
Output Current
(A)
(note 2)
Maximum
Allowable
Circuit
Protection (A)
PF=.8
PF=1
25 kVA
208 V
70
55
(note 1)
25 kVA
220 V
66
52
(note 1)
25 kVA
480 V
30
24
50
30 kVA
208 V
83
66
(note 1)
30 kVA
220 V
78
63
(note 1)
30 kVA
480 V
36
29
60
37 kVA
208 V
104
83
(note 1)
37 kVA
220 V
98
78
(note 1)
37 kVA
480 V
45
36
75
Note 1:
Output circuit protection requirement determined by distribution circuit.
Note 2:
Do not apply continuous loads in excess of rated maximum output current. If the power factor of
the load is not known, use PF=1. The UPS controls will permit transient loads within the limits
described in the OVERLOAD section of this manual.