FirstLine UPS
Form No. 003-2323 Rev B
6
SECTION 3
UPS Setup
This section describes:
Equipment inspection
Floor loading and clearances
Removing and replacing the cabinet panels
Unloading the cabinet(s)
Inspecting The Equipment
If any equipment has been damaged during shipment, keep the shipping and packing
materials for the carrier or place of purchase and file a claim for shipping damage. If you
discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15
days of receipt of the equipment, 2) Send a copy of the damage claim within 15 days to
your service representative.
Floor Loading
When planning the installation, consider the UPS weight for floor loading. The strength of
the installation surface must be adequate for point and distributed loading. The
approximate weights are shown in the following table.
Table 3-Model Floor Loadings
STANDARD MODEL FLOOR LOADING
25-30-37.5 KVA
Maximum Weight
Point Loading
Standard
1253 Lbs (568 kg)
399 lb/in
2
(28 kg/cm
2
)
Extended Run
1765 Lbs (801 kg)
562 lb/in
2
(39 kg/cm
2
)
480 I/O
1855 Lbs (841 kg)
590 lb/in
2
(42 kg/
cm2
)
Clearances
The following clearances are recommended for the FirstLine UPS.
From Front of Cabinet
36” (91.4 cm) working space
From Back of Cabinet
12
” (30.5 cm)
From Side of Cabinet
Minimum 24” (61 cm)