FirstLine UPS
Form No. 003-2323 Rev B
34
To transfer to MBS:
1.
Verify that the bypass source is available (Bypass lamp on UPS mimic display is
green).
2.
Perform a manual transfer to bypass mode on the UPS by pressing and holding the
ESC key while simultaneously pressing the UP-ARROW key.
3.
Verify that the UPS output is ON BYPASS by observing that the lamp associated
with the bypass line at the static switch block on the mimic display is green and that
the lamp associated with the inverter is not lit.
4.
Operate the MBS to put it in bypass mode.
It is now safe to turn off the UPS and close the battery breaker(s). Restart the UPS. To
transfer back to normal mode:
1.
Verify that the UPS is still ON BYPASS by observing the mimic display. If not,
perform a manual transfer to bypass as described, above.
2.
Operate the MBS to put it in normal mode.
3.
Enable automatic transfer by pressing and holding the ESC key while
simultaneously pressing the DOWN-ARROW key. After a few seconds, the mimic
display should show that the static switch has transferred the load to inverter.
UPS Maintenance
The FirstLine UPS is designed to be virtually user maintenance free, requiring only the
occasional wipe with a damp cloth or non-abrasive cleaner.
Spare kits are available for the FirstLine UPS series, please contact Staco Energy Products
Co. service center for details.
For maximum availability of the UPS, the components that are subject to wear should be
replaced as part of a comprehensive preventive maintenance program:
RECOMMENDED REPLACEMENT INTERVALS
Dc Filter Capacitors
5 years
AC Filter Capacitors
5 years
Fans
2 years
Rectifier Chokes
10 years
Batteries
2 to 5 years
1
REPLACEMENT BATTERY
Manufacturer
Cat. Number
Quantity Required
2
China Storage Battery
HR1290W
34 per string
All servicing should be performed by qualified service personnel
.
1
Battery life is highly dependent on the ambient temperature and the number and depth of discharge cycles.
A discharged battery should be recharged as soon as possible. If the battery is left in a discharged state,
irreversible sulfation occurs, reducing the capacity (run-time) of the battery.
2
Some model configurations will use 36 batteries per string. 36 battery models are not part of the UL listing.