7.3.1 Basic Modules
PROFIBUS DP Slave Properties
The configurable properties of the GT200-DP-RS are shown below:
Baud rate (bps):
Configure serial baud rate, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps
can be selected.
Data bits, Parity bit, Stop bits:
8 None 1, 8 Odd 1, 8 Even 1, 8 Mark 1, 8 Space 1 and 8 None 2 can be selected.
Protocol Type:
It depends on the device type (GSD file). For “GT200-DP-RS Modbus Slave V6.0” device, it acts
as a Modbus Slave.
Slave Address:
When Protocol Type is Modbus Slave, configure the slave address of GT200-DP-RS. Range:
1~247.
Transmission Mode:
RTU or ASCII can be selected.
Communication Interfaces
: RS458 and RS232 can be selected, the default is RS485.
Module Properties
Add appropriate modules of different Modbus memory address. The Modbus coil/status/register address begins at
0 (base0) or 1 (base 1), and begins at the first module. The following modules of same address area continue the
address. Users can edit the DP input/output address of these modules.