3. Choosing User Config in protocol type
Configurable parameters are shown as follows:
Baud Rate, Data Bits, Check Bit, Stop Bits, Frame Type, Time interval between Characters, Frame Length, Enable
Auto Sending, Period of Auto Sending, Enable CRC Check, Communication Interface, Time interval between
Character (Sending) and Time interval between Character (Receiving).
Interface of configuration view is shown as follow:
Baud Rate
: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps optional
Data Bits
: 8
Check Bit
: none, odd, even, mark and space optional
Stop Bits
: 1, 2
Frame Type
: Time Interval between Characters, Frame length optional
Time interval between characters
: It is maximum time interval between characters and used to decide whether a
frame is terminated or not. User input, the default is 10, and the range is 10 ~ 60000ms.
Frame Length
: User input, the default is 111 and the range is 1 ~ 223, only valid when the frame type is frame
length.
Enable Auto Sending
: There are Enable and Disable to be selected.
Period of Auto Sending
: User input, the default is 1000 and the range is 10 ~ 60000ms, only valid when the