User Manual
Universal Serial/PROFIBUS DP Gateway
GT200-DP-RS
WWW.SSTCOMM.COM
33
Baud Rate
: 300, 600, 1200, 2400,4800, 9600, 19200, 38400, 57600 and 115200bps optional.
Data Bits
: 8
Check Bit
: none, odd, even, mark and space optional
Stop Bits
: 1, 2
Slave Address
: range is 0~247.
Transmission Mode
: RTU, ASCII
Communication Interface:
There are RS-232 and RS-485 to be selected. (Note: If using the RS-422, here select
RS-485)
Time interval between Characters (Sending)
: T serial port of the GT200-DP-RS will send every byte according
to the time interval. The range of the value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time
interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of the Modbus
protocol)
Time interval between Characters (Receiving)
: T serial port of the GT200-DP-RS will use this time interval as
the judge receiving end basis. The range of the value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the
time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of the
Modbus protocol)